INTRODUCTION
Gate Access (Wireless)
The CAPXL / CAPXLV can communicate wirelessly to LiftMaster
and send email notifi cations if an error occurs in the operator (email notifi cations are confi gured in myQ
operators can be paired with the CAPXL / CAPXLV - one for each primary and auxiliary relay. If using dual gates, program the CAPXL /
CAPXLV to the primary operator.
1
Enter Admin Mode
Flip dipswitch #1 to the ON position to
enter Admin Mode.
ON
NOTE: For new installations press
the login button without entering
information in the Admin Username
and Admin Password fi elds.
4
Press LEARN button on gate
operator again
Press and release the LEARN button
again on the primary operator. The
yellow NETWORK LED will light.
Visit myQBusiness.com for more information on how to set up doors for wireless linking.
PRE-INSTALL
2
Select Outputs and Relay
Select the Outputs tab. Then select the
desired relay on the left-hand side (1
through 4).
ON
5
Select LEARN on display
Select the LEARN button on the
display and the Learn button will go
from blue to red. The gate operator
and the CAPXL / CAPXLV will beep
once and the NETWORK LED on the
gate operator will turn off indicating
programming is successful.
NOTE: 4 beeps/blinks indicate you
are not programming to the primary
operator. Reattempt programming
from the other operator.
INSTALL
NETWORK
®
UL325 gate operators to send open commands, monitor gate position,
19
ACCESS CONTROL
®
Business™). Up to 8 gate
3
Press LEARN button on gate
operator
Press and release the LEARN button
on the primary operator. The green
XMITTER LED will light. NOTE: The
operator will time out of programming
mode after 180 seconds.
6
Validate
Validate functionality by selecting
Test Relay on the CAPXL / CAPXLV
display.