Door Access - LiftMaster myQ Business CAPXL Manual De Instalación

Portal de acceso conectado - alta capacidad
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INTRODUCTION

Door Access

Disconnect power BEFORE making electrical connections. Below is an example of a wiring setup for door access. Door access can be
wired to Door 1, 2, 3, or 4 on the Door Boards.
WIEGAND
KEYPAD
NOTE: For KPR2000
keypad, wire the pink and
black (ground) wires together.
SUPERVISED (DOOR STATUS)
DOOR SENSOR
OR
(SUPERVISED)
EOL (End of Line) Resistor
(1k ohm)
*PRIMARY RELAY
DOOR STRIKE
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
PRE-INSTALL
DOOR SENSOR
(NON-SUPERVISED)
For AC Power:
Install a Siemens
S10K30MOV
(Metal Oxide Varistor)
(provided) or equivalent
Power for Door Strike
(Not Provided)
COMMON
+
NORMALLY OPEN
OR
MAGLOCK
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) (provided)
or equivalent
NORMALLY CLOSED
COMMON
+
Power for Maglock
(Not Provided)
DO NOT use the power
supply for the controller
INSTALL
READER
OR
REQUEST TO EXIT
PROXIMITY
PUSH
SENSOR
BUTTON
OR
NORMALLY CLOSED
AUXILIARY RELAY
Low
Voltage
Power
Supply
Isolation
Relay
NOTE: DO NOT
run high voltage
power within
the CAPXL
enclosure.
NORMALLY OPEN
20
NETWORK
NOTE: The length of the unshielded
wires should be kept to a minimum to
avoid electrical noise.
REQUEST TO EXIT
GROUND
SUPERVISED
NORMALLY OPEN
COMMON
NORMALLY OPEN
COMMON
DOOR 1, 2, 3, or 4
LIGHT
LOAD
LINE
OR
ALARM BYPASS
COMMON
* NOTE: MAGLOCK, door strike
and ALARM BYPASS not
evaluated by UL.
ACCESS CONTROL

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Myq business capxlv

Tabla de contenido