Lutron Technical Support Center 1.800.523.9466 24 hrs / 7 days
Installation
1
Turning Power OFF
Turn power OFF at circuit break er
(or remove fuse).
2
Removing Wallplate and Switch
Remove the wallplate and switch mounting screws.
Carefully remove the switch from the wall (do not remove the wires).
3
Identifying the Circuit Type and Tagging the Wire on the COMMON Terminal of the Switches
3a - Single Location Control
One switch controlling a light fixture:
This switch will be a single-pole. The switch will have insulated wires connected to two screws of the same color
plus a green ground screw.
Ground
(Bare Copper or
Green Wire)
3b - Two-Location Control
Note: Screw
Two switches controlling a light fixture:
placement may be
Both switches will be 3-way. Each switch will have insulated wires connected to three screws plus a green ground
different on the switch.
screw. One of these wires is connected to a screw of a different color (not green) or labeled COMMON. Tag this
Ground (bare copper
wire on both switches to identify when rewiring.
or green wire)
Different colored
screw (Common)
Tag
3c - Three or More-Location Control
Three or more switches controlling a light fixture:
Note: Screw
placement may
Two switches will be 3-way and any others will be 4-way. Tag the two 3-way switches as in the Two-Location
be different on the
diagram above. The 4-way switch will have insulated wires connected to four screws plus a green ground screw.
switch.
Tag the two same-color insulated wires that are connected to opposite colored screws. Follow this procedure for
Same colored
each 4-way switch.
screw (or
marked IN or
OUT)
Ground
Tags
(bare copper or green wire)
4
Disconnecting the Switch Wires
Important Note: The wall switch may have two wires attached to the same screw (see illustrations below for examples). Tape these two wires
together before disconnecting. When rewiring, connect wires to the Electronic Switch the same way they were connected to the switch.
One wire in the backwired hole
One continuous
Push-in Terminals:
and one to the screw.
wire to the screw.
Insert screwdriver. Pull wire out.
5
Wiring
When making wire connections, follow the recommended strip lengths and combinations for the supplied wire connector. Note: All wire connectors
provided are suitable for copper wire only. For aluminum wire, consult an electrician.
Trim or strip wallbox wires to the length indicated by the strip gauge on the back of the Electronic Switch.
Wire connector:
Push-in terminals:
Use to join 14 AWG
Insert wires fully.
(1.5 mm
2
) or 12 AWG
Note: Push-in terminals are
(2.5 mm
) ground wire
for use with 14 AWG (1.5 mm
)
2
2
to 18 AWG (0.75 mm
)
solid copper wire only. DO NOT
2
Electronic Switch
use stranded or twisted wire.
ground wire.
Twist wire
connector tight.
•
For installations involving more than one control in a wallbox, refer to Multigang Installations before beginning.
•
Use the screw or push-in terminals when making connections on the Electronic Switch or Companion Switch.
•
Wire all controls before mounting.
5a - Single-Location Control
Install the Electronic Switch:
Brass screw
Dimmer
•
Connect the
green ground wire on the Electronic Switch to the bare copper
or green ground wire in the wallbox. (See Important Note 3 on other side.)
•
Connect either of the wires removed from the switch to the
black screw
terminal on the Electronic Switch.
•
Connect the remaining wire removed from the switch to the
brass screw
terminal on the Electronic Switch.
•
Tighten the
blue screw terminal on the Electronic Switch. It is not used
Black screw
in a single-pole circuit.
Ground
Green wire
•
Install LUT-MLC when applicable. Refer to "Wiring the LUT-MLC"
instruction sheet for installation procedure.
5b - Two-Location Control
One location will be replaced with an Electronic Switch and the other with a Companion Switch.
Important: In any 120 V 3-way circuit use MA / MSC-AS Companion Switch. In any 277 V 3-way circuit use MA / MSC-AS-277 Companion Switch.
Install the Electronic Switch:
Brass screw
Blue screw
•
Connect the
green ground wire on the Electronic Switch to the bare copper or green ground wire in the wallbox. (See Important Note 3 on other side.)
•
Connect the tagged wire removed from the switch in step 3b to the
black screw terminal on the Electronic Switch.
•
Connect one of the remaining wires removed from the switch to the
brass screw terminal on the Electronic Switch.
Tag
•
Connect the remaining wire removed from the switch (note wire color) to the
Install the Companion Switch
Electronic Switch or
Black screw
Ground
(MA / MSC-AS or MA / MSC-AS-277):
Companion Switch
Green wire
•
Connect the
green ground wire on the Electronic
Switch to the bare copper or green ground wire
Blue screw
Brass screw
Brass
in the wallbox. (See Important Note 3 on other side.)
Hot/Live
Black
•
Connect the wire tagged in step 3b to the
brass screw
terminal on the Companion Switch.
120-277 V~
50/60 Hz
•
Connect the same color wire connected to the
blue
Tag
screw terminal on the Electronic Switch (wire color noted above)
Wallbox
to the blue screw terminal on the Companion Switch.
Two-Location Wiring Diagram
•
Connect the remaining wire removed from the switch
to the black screw terminal on the Companion Switch.
Green wire
Ground
Black screw
•
Install LUT-MLC when applicable. Refer to "Wiring the LUT-MLC" instruction sheet for installation procedure.
5c - Three or More-Location Control
One location will be replaced with an Electronic Switch and the others with Companion Switches. Only one Electronic Switch can be used with up to nine Companion Switches.
Important: In any 120 V 3-way/4-way circuit use MA / MSC-AS Companion Switches. In any 277 V 3-way/4way circuit use MA / MSC-AS-277 Companion Switches.
Tags
Replace the 4-way switch(es):
Blue
Brass screw
Note: 4-way switches may be replaced with either an Electronic Switch or a Companion Switch.
screw
•
Connect the
green ground wire on the Electronic Switch or Companion Switch to the bare copper or green ground wire in the wallbox.
(See Important Note 3 on other side.)
•
Connect both of the wires tagged in step 3c (noting their color) to the
(one wire to the screw and the other to the push-in terminal).
•
Connect one of the remaining wires removed from the switch to the
brass screw terminal on the Electronic Switch or Companion Switch.
•
Connect the remaining wire removed from the switch to the
black screw terminal on the Electronic Switch or Companion Switch.
Black screw
Ground
Electronic Switch or
Green wire
Companion Switch
Brass screw Blue screw
Replace the 3-way switches:
Electronic Switch or
•
Connect the
green ground wire on the
Companion Switch
Tag
Electronic Switch or Companion Switch to
the bare copper or green ground wire in
Brass
Blue
the wallbox. (See Important Note 3 on other side.)
Hot/Live
Black
•
Connect the wire tagged in step 3b to the
brass screw terminal on the Electronic Switch.
120-277 V~
Green
50/60 Hz
•
Connect the same color wire connected to the
Black screw
Ground
Wallbox
Ground
blue screw terminal on the Electronic Switch
Green wire
Three or More Location Wiring Diagram
Electronic
(wire color noted above) to the blue screw terminal
Switch or
on the Companion Switch.
Companion
Switch
•
Connect the remaining wire removed from the switch to the
black screw terminal on the Electronic Switch or Companion Switch.
•
Install LUT-MLC when applicable. Refer to "Wiring the LUT-MLC" instruction sheet for installation procedure.
6
Mounting Switches to Wallbox
Form wires carefully into the wallbox, mount and align Electronic Switch (and Companion Switches).
Attach Claro
or Satin Colors
Wallplate(s) (sold separately).
®
®
7
Turning Power ON
Turn power ON at circuit breaker (or replace fuse).
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
Centro de Soporte Técnico de Lutron +1.888.235.2910 las 24 horas / los 7 días de la semana
Instalación
1
Desconectar la alimentación
WARNING
Shock Hazard. May result in serious injury or
death. Turn off power at circuit breaker before
Desconecte la alimentación en el
installing the unit.
disyuntor (o quite el fusible).
Peligro de choque. Podría resultar en
2
ADVERTENCIA
lesiones graves o la muerte. Desconecte la
Remoción de la placa de pared y del interruptor
alimentación en el cortacircuito antes de
Retire la placa de pared y los tornillos de montaje del interruptor.
instalar el unidad.
Retire cuidadosamente el interruptor de la pared (no quite los cables).
Danger d'électrocution. Peut causer le
3
AVERTISSEMENT
Identificación del tipo de circuito y etiquetado del cable en el borne "COMÚN" de los interruptores.
décès de la personne ou de graves lésions.
Couper le courant (off) au disjoncteur
avant de procéder à l'installation.
3a – Control desde un solo lugar
Tierra
(cable verde o de
cobre desnudo)
3b – Control desde dos lugares
Nota: La ubicación
de los tornillos puede
ser diferente en el
interruptor.
Tierra (cable verde o
de cobre desnudo)
Tornillo de distinto
color (Común)
3c – Control desde tres o más lugares
Nota: La ubicación
de los tornillos puede
ser diferente en el
interruptor.
Tornillo del mismo
color (o marcado
como IN o OUT)
Tierra
(cable verde o de cobre desnudo)
4
Desconexión de los cables del interruptor.
Nota Importante: Su Atenuador de pared puede tener dos cables conectados a un mismo tornillo (vea los ejemplos ilustrados a continuación). Una
ambos cables con cinta adhesiva antes de desconectarlos. Cuando realice el cableado nuevamente, conecte los cables al Interruptor Electrónico de
la misma forma en que estaban conectados al Atenuador que se reemplaza.
Un cable en el orificio posterior
Screw Terminals:
Looped Wire:
para cables y uno al tornillo.
Turn screws to loosen.
Turn screw to loosen.
5
Cableado
Cuando se hagan las conexiones de los cables, la sección sin aislamiento debe respetar las combinaciones y longitudes recomendadas para el
conector de cable provisto. Nota: Todos los conectores de cable que se proveen son para cables de cobre solamente. Para cables de aluminio,
consulte a un electricista.
Recorte o pele los cables de la caja de empotrar hasta la medida indicada en el reverso del Interruptor electrónico.
Screw terminals:
Conector de cables:
Tighten securely.
Use para unir cables de tierra
Note: Screw terminals are for
de 1,5 mm
2
(14 AWG) o
use with 12 AWG (2.5 mm
)
2
2,5 mm
(12 AWG) al cable
2
or 14 AWG (1.5 mm
) solid
2
de tierra de 0,75 mm
copper wire only. DO NOT
(18 AWG) del Interruptor
use stranded or twisted wire.
electrónico.
Para instalaciones de más de un control en una misma caja, consulte Multigang Installations (Instalaciones con varios dispositivos acoplados) antes de comenzar.
Use los bornes de tornillo o de presión cuando haga conexiones en el Interruptor Electrónico o en el Interruptor Accesorio.
Finalice el cableado de todos los controles antes del montaje.
5a – Control desde un solo lugar
Electronic Switch
Fixture
Tornillo de latón
Brass
Blue
Hot/Live
Black
Load
LUT-MLC
120-277 V~
50/60 Hz
Green
Ground
Wallbox
Neutral
Tornillo negro
Single Location Wiring Diagram
Cable verde
5b – Control desde dos lugares
Una ubicación se reemplazará con un Interruptor Electrónico y la otra con un Interruptor Accesorio.
Importante: En circuitos de 120 V 3 vías use el Interruptor Accesorio MA / MSC-AS. En los circuitos de 277 V de 3 vías use el interruptor Accesorio MA / MSC-AS-277.
Tornillo de latón
Tornillo azul
Etiquetas
blue screw terminal on the Electronic Switch.
Tornillo negro
Cable verde
Electronic Switch or
Companion Switch
Fixture
Tornillo
de latón
Blue
Brass
Blue
Load
LUT-MLC
Black
Etiquetas
Green
Green
Ground
Ground
Neutral
Wallbox
Tierra
Tornillo negro
5c – Control desde tres o más lugares
Una ubicación será reemplazada por un Interruptor Electrónicoy las demás con Interruptores Accesorios. Se puede usar sólo un Interruptor Electrónico con un máximo de
nueve Interruptores Accesorios.
Importante: En circuitos de 120 V de 3 o 4 vías, use Interruptores Accesorios MA / MSC-AS. En los circuitos de 277 V de 3 o 4 vías,
Tornillo
de latón
Tornillo
azul
blue screw terminal on the Electronic Switch or Companion Switch
Tornillo negro
Interruptor Electrónico
o Accesorio
Tornillo de latón
Electronic Switch or
Electronic Switch or
Companion Switch
Companion Switch
Fixture
Etiqueta
Brass
Blue
Brass
Blue
Load
LUT-MLC
Black
Black
Green
Green
Ground
Ground
Neutral
Wallbox
Wallbox
Tierra
Interruptor
Electrónico o
Accesorio
6
Montaje de los interruptores en la caja de empotrar.
Align Electronic
Coloque los cables cuidadosamente en la caja de empotrar, monte y alinee el Interruptor Electrónico
Switch and
Start screws.
(y los Interruptores Accesorios).
tighten screws.
Coloque la o las placas de pared Claro
7
ENCENDIDO de la alimentación
Conecte la alimentación en el disyuntor
(o reemplace los fusiles).
www.lutron.com
Printed in the U.S.A. 10/10 P/N 030-1334 Rev.B
WARNING
Shock Hazard. May result in serious injury or
death. Turn off power at circuit breaker before
installing the unit.
ADVERTENCIA
AVERTISSEMENT
Un interruptor que controla una lámpara:
Este interruptor será unipolar. El interruptor tendrá cables aislados conectados a dos tornillos del mismo color más
un tornillo verde de tierra.
Dos interruptores que controlan una lámpara:
Ambos interruptores serán de 3 vías. Cada interruptor tendrá cables aislados conectados a tres tornillos más un tornillo
de tierra de color verde. Uno de estos cables estará conectado a un tornillo de distinto color (no verde) o etiquetado
como COMÚN. Identifique este cable en ambos interruptores para poder distinguirlo cuando vuelva a cablear.
Etiquetas
Tres interruptores o más que controlan una lámpara:
Dos interruptores serán de 3 vías y los otros de 4. Rotule los dos interruptores de 3 puntos tal como se muestra
en el diagrama anterior, Control desde dos lugares. El interruptor de 4 vías tendrá cables aislados conectados a
cuatro tornillos, además de un tornillo de tierra de color verde. Rotule los dos cables aislados del mismo color que
están conectados a tornillos de colores opuestos. Siga este procedimiento para cada interruptor de 4 vías.
Etiquetas
Un cable continuo
Bornes a presión:
Bornes de tornillos:
conectado al tornillo.
Inserte el destornillador.
Afloje los tornillos.
Tire el cable hacia fuera.
Terminales a presión:
Terminales de Tornillo:
Inserte los cables totalmente.
Ajústelos en forma segura.
Nota: Los terminales a presión sólo
Nota: Las terminales de tornillo
deben utilizarse con cables sólidos
sólo deben usarse con cables
Electronic Switch
de cobre de 1,5 mm
2
(14 AWG).
sólidos de cobre de 2,5 mm
2
NO los use con cables retorcidos
(12 AWG) o 1,5 mm
ni trenzados.
NO los use con cables retorcidos
Gire el conector de
ni trenzados.
cable para afirmarlo.
Interruptor Electrónico
Instale el Interruptor electrónico:
Atenuador
•
Conecte el cable
verde de tierra del Interruptor Electrónico al cable de cobre desnudo.
Latón
o cable de tierra verde de la caja de empotrar (vea la Nota Importante 3 en el reverso.)
Vivo
Negro
•
Conecte uno de los cables retirados del interruptor al terminal de tornillo
negro
120-277 V~
del Interruptor Electrónico.
Verde
50/60 Hz
•
Conecte el cable restante extraído del interruptor al borne de tornillo de
latón
del Interruptor Electrónico.
Caja de empotrar
Diagrama de cableado para control
•
Ajuste el borne de tornillo
azul del Interruptor Electrónico.
desde un solo lugar
No se usa en un circuito unipolar.
Tierra
•
Instale LUT-MLC si corresponde. Consulte el procedimiento de instalación en la hoja de instrucciones "Cableado de LUT-MLC".
Instale el Interruptor electrónico:
•
Conecte el cable
verde de tierra del Interruptor Electrónico al cable de cobre desnudo o cable de tierra verde de la caja de empotrar
(vea la Nota Importante 3 en el reverso.)
•
Conecte el cable rotulado extraído del interruptor en el paso 3b al borne de tornillo
negro del Interruptor Electrónico.
•
Conecte uno de los cables restantes retirado del interruptor al terminal de tornillo de
latón del Interruptor Electrónico.
•
Conecte el cable restante retirado del interruptor (anote el color del cable) al terminal de tornillo
azul del Interruptor Electrónico.
Interruptor
Interruptor
Instale el Interruptor Accesorio
Electrónico o Accesorio
Electrónico o Accesorio
Tierra
(MA / MSC-AS o MA / MSC-AS-277):
Tornillo azul
•
Conecte el cable
verde de tierra del Interruptor Electrónico
al cable de cobre desnudo o cable verdede tierra de la
Latón
Azul
Latón
caja de empotrar. (Vea la Nota Importante 3 en el reverso.)
Vivo
Negro
Negro
•
Conecte el cable rotulado en el paso 3b al terminal de
120-277 V~
Verde
Verde
tornillo latón del Interruptor Accesorio
50/60 Hz
•
Conecte el cable del mismo color que el conectado al
borne
Tierra
Caja de empotrar
Caja de empotrar
de tornillo azul en el Interruptor Electrónico (el color del cable
Diagrama de cableado para control desde dos lugares
se anotó anteriormente) al borne de tornillo azul del
Interruptor Accesorio.
Cable verde
•
Conecte el cable restante extraído del interruptor al
borne de tornillo de negro del Interruptor Accesorio.
•
Instale LUT-MLC si corresponde. Consulte el procedimiento de instalación en la hoja de instrucciones "Cableado de LUT-MLC".
use
Interruptores Accesorios MA / MSC-AS-277.
Reemplace los interruptores de 4 vías:
Etiquetas
•
Nota:
Los interruptores de 4 vías pueden ser reemplazados con un Interruptor Electrónico o un Interruptor Accesorio.
•
Conecte el cable
verde de tierra del Interruptor Electrónico o Accesorio al cable de tierra verde o de cobre desnudo de la caja de empotrar.
(Vea la Nota Importante 3 en el reverso).
•
Conecte ambos cables rotulados en el paso 3c (anotando su color) al borne de tornillo
azul del Interruptor Electrónico o Accesorio
(un cable al borne de tornillo y el otro en el borne a presión).
•
Conecte uno de los cables restantes retirados del interruptor al terminal de tornillo
latón del Interruptor Electrónico o Accesorio.
•
Conecte el cable restante retirado del interruptor al terminal de tornillo de
negro del Interruptor Electrónico o Accesorio.
Tierra
Cable verde
Interruptor
Interruptor
Interruptor
Electrónico o Accesorio
Electrónico o Accesorio
Electrónico o Accesorio
Tornillo azul
Reemplace los interruptores de 3 vías:
•
Conecte el cable verde
de tierra del
Interruptor Electrónico o Interruptor Accesorio
Latón
Azul
Latón
Azul
al cable de tierra verde o de cobre desnudo
Vivo
Negro
de la caja de empotrar. (Consulte la Nota
Negro
importante 3 en el reverso).
120-277 V~
Verde
50/60 Hz
Verde
•
Conecte el cable rotulado extraído del
Tierra
Tierra
interruptor en el paso 3b al borne de
Caja de empotrar
Caja de empotrar
Caja de empotrar
Tornillo negro
tornillo latón del Atenuador o Interruptor Electrónico.
Diagrama de cableado para control desde tres o más lugares
Cable verde
•
Conecte el cable del mismo color que el conectado
al borne de tornillo azul en el Interruptor Electrónico (el color del cable se anotó anteriormente) al borne de tornillo azul del Interruptor Accesorio.
•
Conecte el cable restante retirado del interruptor al terminal de tornillo de
negro del Interruptor Electrónico o Accesorio.
•
Instale LUT-MLC si corresponde. Consulte el procedimiento de instalación en la hoja de instrucciones "Cableado de LUT-MLC".
Inserte y comience
a atornillar los
tornillos.
o Satin Colors
(se venden por separado).
TM
TM
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299, E.U.A.
Peligro de choque. Podría resultar en
lesiones graves o la muerte. Desconecte la
alimentación en el cortacircuito antes de
instalar el unidad.
Danger d'électrocution. Peut causer le
décès de la personne ou de graves lésions.
Couper le courant (off) au disjoncteur
avant de procéder à l'installation.
Cable en bucle:
Gire el tornillo
para aflojar.
2
(14 AWG).
2
Aplique
Azul
Carga
LUT-MLC
Tierra
Neutro
Aplique
Azul
Carga
LUT-MLC
Tierra
Neutro
Aplique
Latón
Azul
Carga
LUT-MLC
Negro
Verde
Tierra
Neutro
Alinee el Interruptor
Electrónico y afirme
los tornillos.
www.lutron.com
Impreso en los E.U.A. 10/10 P/N 030-1334 Rev.B
Shock Hazard. May result in serious injury or
WARNING
death. Turn off power at circuit breaker before
installing the unit.
Peligro de choque. Podría resultar en
ADVERTENCIA
lesiones graves o la muerte. Desconecte la
alimentación en el cortacircuito antes de
instalar el unidad.