5. Operation
5.5 Condensate Valve Setup
The SRCOOL33K features a built-in condensate removal system that evaporates condensate removed from the air by atomizing it into the
condenser air stream. During normal operation, the amount of water removed from the air is minimal. However, if the amount of water
removed from the air exceeds the capability of the internal removal system (0.85 gal/hr; 3.22 L/hr), the user must re-route the drainage to a
nearby drain using the provided auxiliary drain line.
1
Make sure that the unit is powered down and disconnected from AC input.
2
Open side panel and locate the condensate valve (for more information, see 6.4 Installation in High-Humidity Environments in the
Installation Manual).
3A
Internal Evaporation
Setting: Turn the valve
connected to the evaporator
line counterclockwise and the
valve to the auxiliary drain line
clockwise.

6. Troubleshooting

Locate the problem and review possible solutions in the following table. If the problem persists, visit www.tripplite.com/support to obtain
service.
Problem
Fan fails to start.
Cooling unit cannot achieve
setpoint.
Excess water in the unit.
Cooling unit noise level is
excessive.
Water around cooling unit.
Internal Evaporation
Setting
WATER
FROM
PUMP
TO
EVAPORATOR
Possible Cause
Faulty fan.
Dirty filter.
Dirty coil.
Improper fan speed.
Room humidity too high.
Dirty filter.
Improper fan speed.
Condensate drain hose not
connected or not properly routed.
Leak in drain system.
Cooling unit not properly leveled.
Piping insulation damaged.
External Drain
Internal Evaporation
Setting
Setting
3B
External Drain Setting:
Turn the valve connected
to the auxiliary drain line
WATER
WATER
counterclockwise and the
FROM
FROM
valve to the evaporator line
PUMP
PUMP
clockwise.
TO
TO
EXTERNAL
EVAPORATOR
DRAIN
17-10-239 96-A2AB_RevX1
Possible Solution
Replace the fan.
Clean filter.
Clean coil.
Fan speed set to Low. Set fan speed to Auto or increase fan speed.
Add drain line.
Adjust setpoint on humidifying equipment.
Improve room sealing.
Clean filter.
Select lower fan speed.
Verify proper connection of condensate drain hose.
Locate and repair leak.
Adjust cooling unit's leveling feet.
Locate damage area and repair insulation.
7
External Drain
Setting
WATER
FROM
PUMP
TO
EXTERNAL
DRAIN
17-10-239 96-A2AB_RevX1