Code 011: Detection of various systems in the same channel
Wait for the LED D2 is turned off. When the LED is off, there are two cases that can
happen:
• The D100 LED lights and stays fixed, so you have to wait until the time of association
ends.
• The LED D100 starts flashing – you have to press the switch SW100 of association
and wait again the association time.

9. SELF-TESTING PROCESS

It is possible to make a self-testing process of the system using the red D13 LED of Self-
testing process (see Fig. 2).
To run the test, put the thermostat in STOP mode. This gives a diagnosis of the status of the
Alarm Bridge and the Return Probe.
If an integration gateway is connected, only the Alarm Bridge will be tested.
Check the following table for the meaning of the self-testing process:
Probe in open circuit or not connected 
Probe in short-circuit 
Alarm bridge not connected 
Temperature measured in return in the
protection zone (T<6ºC, 8ºC and 10ºC or
T>32ºC, 34ºC and 36ºC)
If there are more than two errors, the error priority indicates what combination of flashes
would be displayed. That is to say, if the priorities are 2 and 5, it will only flash 4 times, since
error 2 has higher priority.
8
The temperature limit depends on the parameter settings of TRET. For more information, please refer to section
6.1.
66
Detected event
8
Nº of flashes
priority
2
3
4
6
Error
3
1
2
4