Brief Description; Instructions For Safe Use; Special Conditions For Safe Use - Weidmuller Klippon Instrucciones Para Un Uso Seguro

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Brief Description

The KDSU type cable gland is for outdoor use in
the appropriate Hazardous Areas with armoured,
un- armoured, braided and screened cable. It gives
environmental protection to IP66, IP68 and Deluge.
A variant giving electrical continuity to a lead sheath
is available.A termination suitable for EMC protection
can be made using armoured cables with this gland.
Warning!
Please read these instruction carefully before
installation.
These glands should not be used in any application
other than those mentioned here or in our Data
Sheets, unless Weidmuller states in writing that the
product is suitable for such application. Weidmuller
can take no responsibility for any damage, injury or
other consequential loss caused where the glands are
not installed or used according to these instructions.
This leaflet is not intended to offer advice on the
selection of cable glands. Further guidance can be
found in the standards listed overleaf.
Interpretation of Markings
Markings on the outside of this gland carry the
following meanings: KDSU [a] [b] [c] [d] [e] [f] [ggg]
Where: KDSU = Klippon
Double Seal Universal
®
[a] = Entry thread
[b] = Main component material
(B = brass, S = stainless steel)
[c] = Seal material
(S = silicone, N = Neoprene)
[d] = Continuity for lead sheath
(L = yes, O = no)
[e] = Plating
(Sc = self coloured, Ni = Nickel, Zi = zinc)
[f] = Reduced bore outer seal
(1 = yes, 2 = no)
[ggg] = Gland size (Gsss) (e.g. G20S)
2493020000/00/09.16
Certificate Numbers
(ATEX) SIRA 05ATEX1285X
(IECEx) IECEx SIR 05.0067X
Protection Concept, EPL's and Gas Groups:
Ex d IIC Gb / Ex e IIC Gb / Ex ta IIIC Da
Environmental Protection:
IP66 / IP68 (50 metres for 7 Days)
ATEX (EU Directive 2014/34/EU) Markings:
T
II 1D
T
II 2G

Special Conditions for Safe Use

1. These glands must not be used in enclosures
where the temperature at the point of mounting
is outside the range of -35°C to +90°C using
neoprene seals, or –60° to +180°C using silicone
seals.
2. When the gland is used with increased safety and/
or dust protected equipment, the entry thread
shall be suitable sealed to maintain the ingress
protection rating of the associated enclosure.
3. If these cable glands only grip the cable sheath of
the cable and do not clamp the cable armour or if
they are used to terminate unarmoured, braided
or screened cables, then they shall only be used
for fixed installations, hence the cables shall be
effectively clamped to prevent pulling or twisting.
4. These glands, when installed in accordance
with the manufacturers instructions and with an
appropriate enclosure on which they are fixed, are
capable of providing an ingress protection of IP66
and IP68 (50 metres 7 days)
5. Where glands without sealing rings are installed in
protection by enclosure (Ex t) equipment for use
in explosive dust atmospheres, they may only be
fitted into enclosures offering a minimum of 5 full
threads, in accordance with EN 60079-31:2014
clause 5.1.2.

Instructions for safe use

5

Publicidad

Tabla de contenido
loading