Safety
Safety instructions
Make sure that any person installing, taking into operation
and operating the safety detector:
• Is technically qualified and competent.
• Fully comply with these assembling instructions.
Improper operations or misuse could cause danger to:
• life and limb
• the equipment and other assets of the operator
• the equipment proper function
Safety instructions in this manual are shown in three diffe-
rent forms to emphasize important information.
WARNING
This information indicates particular danger to life and health.
Disregarding such a warning can lead to serious or fatal injury.
CAUTION
This information indicates particular danger to equipment and/
or other property of the user. Serious or fatal injury cannot be
excluded.
This notes give important or specific information concerning the
equipment.
Safety notes on the equipment operation
Electrical installation is subject to the relevant national
safety rules.
It is mandatory to connect the grounding cable because of
safety reason.
CAUTION
Installation, electrical connection and fitting the device have to
be carried out by qualified personnel and only in accordance to
this instruction manual.
It is responsibility of the user to make sure that the device is
used for specified application only.
For safety matters, please avoid any unauthorized and
improperly works.
WARNING
All relevant fire protection regulation must be strictly observed.
4
NOTE
Product description
The RIS2 integrated safety detector is composed by a
rugged plastic body, watertight and resistant to extreme
climates, with a series of instruments which keep con-
stant control of the following operating conditions of the
transformer:
• Pressure
• Pressure switch: closes/opens a circuit on pressure
ranging (from 100 up to 500 mbar).
• Temperature
• Thermometer: visual indication of oil temperature and
max. temperature reached.
• "T2" Thermostat switch: (alarm) closes/opens a circuit
at a predetermined temperature level (from 30°C up to
120°C).
• "T1" Thermostat switch: (stop) closes/opens a circuit
at a predetermined temperature level (from 30°C up to
120°C).
• Oil level
• Indicator: visual indicator of slight oil level variation.
• Detector: visual detector of significant oil level
variation through the closing/opening of an electric
circuit.
• Gassing
• Detector: closes/opens a circuit when the max. gas
volume is reached (max. 170 cm
WARNING
It is important to observe the limit values indicated on the
nameplate and in the manual before commissioning the device.
Installation
Mounting instruction
Application to a transformer tank
• Ø 60 mm ± 1 mm diam. hole on the tank
• Flat gasket (provided with the unit)
• Stainless steel fixing brackets (4 pcs packed)
• Stainless steel flat washers according to UNI 6592
Ø 8,4 mm (4 pcs packed)
• Stainless steel spring washers according to UNI 1751
Ø 8,4 mm (4 pcs packed)
• Stainless steel M8 nuts according to UNI 5588
(4 pcs packed).
Tighten the nuts in position 1,2,3,4 with torque nut 3 Nm
to 4 Nm in a cross pattern; repeat the operation following
the same sequence until the suggested value (6 Nm to 8
Nm) is reached.
Due to the deformation of the cover during lifting of the
transformer, an oil leak could be possible. It is suggested
to use covers of suitable thickness (min. 6-8 mm).
INTEGRATED SAFETY DEVICES RIS2
)
3