According the cooker hood you own:
Lamp 40W max (E14) or Neon lamp 14W
max or PL lamp 11W max (model with 1 PL
lamp) or PL lamp 9W max (model with two
PL lamps)
4. Reclose the protective shield for the lamp.
Before calling for repair service because the
hood fails to light up, make sure the lamps are
well inserted.
Warning!
— The hood cannot be connected to flues of
other appliances that run on energy sources
other than electricity.
— When the hood is used at the same time of
other appliances that run on energy sources
other than electricity, provision must be
made for an adequate supply of air.
— No food must be cooked flambé underneath
the hood.
The use of an unprotected flame is
dangerous for the filters and could cause
fires.
Therefore, never use an open flame under
the hood. When frying foods, never leave
the pan alone because the cooking oil could
flare up.
— Please, keep to the provisions of official
directives regarding the question of fume
discharge.
— The manufacturers refuse to accept any
responsibility for damage to the hood or its
catching on fire because of failure to observe
the above instructions.
Installation
Do not tile, grout or silicone this appliance to the
wall. Surface mounting only.
Do not fix chimney flue to furniture or fly over
shelves unless the chimney flue can be easily
removed, in case maintenance is ever required.
These minimum distances between hobs and
grease filter must be observed:
Minimum 650 mm - electric hobs
Minimum 700 mm - gas or mixed hobs.
Electric connection
The electrical tension must correspond to the
tension noted on the label placed inside the cooker
hood. Connect the electrical plug, where provided,
to the an easily accessible outlet in conformity
with local standards in force.
Where an electrical plug is not provided (for direct
connection to electrical network) place a standards
GB
approved bipolar switch with an aperture
distance of not less than 3mm (accessible) from
the contacts. The manufacturers are not liable for
any problems caused by the user's failure to
observer the above instructions.
Systems available
Two systems are available:
Exhaust mode
Vapours are extracted outside through an
exhausting pipe that is affixed to the connection
ring above the hood.
Diameter of the exhausting pipe must be equal
to that of the connection ring.
Exhausting pipe and fixing brackets are not
supplied
In the horizontal runs the duct must be slightly
slanted (about 10°) and directed upwards to
vent the air easily from the room to the outside.
Attention!
If the hood is supplied with carbon filter,
then it must be removed.
Filter version
The air is filtered through a carbon filter (for its
installation see paragraph "Carbon filter") and
recirculated into the room.
An exhausting pipe, for the expulsion of fumes,
should be mounted from the connection ring to the
top of the wall cabinet where an outlet hole must
be made (exhausting pipe and fixing brackets are
not supplied).
Attention!
If the hood is not supplied with carbon filter,
then it must be ordered and mounted.
This version is used when there is no exhaust
duct for venting outdoors or when it is impossible
to install one.
Important:
For the 74,8 cm hood (Fig. 6-7)
Before using the hood, ensure that the inside
grids (G-Fig. 8)are open (Exhaust mode) or closed
(Filter version).
10