Installation Instruction of Outdoor Manifold (B)
Available for the manifold of 4 outdoor units combination
C omponent Lis t
A c c es s or y
box nam e
E V RO - B P 2D
ID:31 8
.
ID:25.4
E V RO - B P 3D
ID:31 8
.
ID:25.4
E V RO - B P 4D
ID:31 8
.
ID:25.4
Essentials for Selection
How to select the connection tube assembly
for outdoor units .
Number of
Pipe box name
outdoor units
Two
EVRO-BP2 D
Three
EVRO-BP3 D
Four
EVRO-BP4 D
E s s entials for Cutting
Manifold
Site piping
Cut at the middle
of connecting portion
Instruction for Installation
1)
Select manifolds in accordance with the guidelines for the designed model according to the number of the outdoor unitsconnected in parallel.
2)
Cut undesired portion by the dedicated tools (such as cutters) in accordance with the actual pipe diameter size.
Taking the EVRO-BP2D for gas side as an example, the operating steps are shown as follows:
a. After the model EVRO-BP2D is selected, the obtained actual material is shown in Figure 1.
Assume the current unit outlet pipe is
φ
according to Figure 2.
b. The independent pipe Q1 and Q3 shall be welded with U-shaped tee Q4 according to Figure 2.
Q2 since the piping diameter can be directly matched with the U-shaped tee at the unwelded end.
c. The manifold assembly shall be welded with the pipe at site according to Figure 3.
3) Pay special attention to the treatment of the following special circumstances:
a. When the actual pipe diameter matches with the U-shaped tee at the un-welded end, weld the pipe with the U-shaped tee directly.
b. For the pipe Q3 and Q7, cut it at the root of the flared end in according to Figure 4 if it is necessary.
4) The installation diagram is for reference only, please be subject to the actual product. The product may be upgraded without notice.
M anifold as s em bly for gas s ide
ID:31 8
.
ID:25.4
ID:31 8
ID:31 8
.
ID:25.4
ID:25.4
Tube Assembly Comparison Table
Tube assemblies for R410A outdoor unit
Ta b le 2
Capacity of
outdoor unit
8HP
10HP
12、14HP
16HP
18~24HP
26~34HP
36~54HP
56~66HP
68~82HP
84~96HP
Note the Hor iz ontal Loc ation
Direction A
Within
±10°
Horizontal tilt
angle within ±10°
A
31.8 and the main pipe is
φ
38.1, cut the independent pipe Q1 manifold assembly
ID:15 88
ID:12 7
ID:15 88
.
ID:12 7
E q u iva le n t le n g th o f
a ll p ip e s <9 0 ml
Gas pipe
Liquid pipe
φ19 .1
φ9. 5
φ22 .2
φ9. 5
φ25 .4
φ12. 7
φ28 .6
φ12. 7
φ28 .6
φ15. 9
φ31 .8
φ19. 1
φ38 .1
φ19. 1
φ41 .2
φ19. 1
φ44 .5
φ22. 2
φ50 .8
φ25. 4
Direction B
Within
±10°
Within
±10°
B
And discard the independent pipe
P l e a s e r e a d th i s m a n u a l c a r e fu l l y b e fo r e i n s ta l l a ti o n
a n d i n s ta l l a c c o r d i n g to th e i n s tr u c ti o n .
M anifold as s em bly for liquid s ide
ID:15 88
.
ID:12 7
.
ID:15 88
.
.
ID:12 7
.
.
ID:15 88
.
.
ID:12 7
.
.
Ta b l e 3
E q u iva le n t le n g th o f
a ll p ip e s ≥9 0 m
Gas pipe
Liquid pipe
φ 2 2. 2
φ 12. 7
φ 2 5. 4
φ 12. 7
φ2 8. 6
φ 15. 9
φ3 1. 8
φ 15. 9
φ3 1. 8
φ 19. 1
φ3 8. 1
φ 22. 2
φ4 1. 2
φ 22. 2
φ4 4. 5
φ 22. 2
φ5 4. 0
φ 25. 4
φ5 4. 0
φ 28. 6
N o t e s
1)
Pay attention to the distance of straight horizontal pipe
0 . 5 m o r m o re
0 . 5 m o r m o re
Outdoor
Unit
A. The distance of the straight horizontal pipe between the
two neighboring manifolds shall be greater than or equal to 0.5m.
B. The distance of the straight horizontal pipe connecting the
indoor unit after the manifold shall be greater than or equal to 0.5m.
Q2
Q1
Q4
Figure 1
Q1
Q4
Figure 3
Ta b l e 1
ID:15 88
.
ID:12 7
.
.
Outdoor
Outdoor
Unit
Unit
Abandon
Q2
Q4
Q3
Q3
Cut from here
Figure 2
Q3
Q7
Cut from
essential part
Figure 4
V.1