ADV/FX/AUX-------------P00
aux output
Remote
function
DOWN INC
DEC
ADV/FX/AUX---------------P00
genalert
on setpoint
DOWN INC
DEC
ADV/FX/AUX---------------P00
loadshed
off setpoint
DOWN INC
DEC
ADV/FX/AUX---------------P00
ventfan
on setpoint
DOWN INC
DEC
• From the Remote aux output function screen, press
the <DOWN> soft key. This will bring up the first of
several screen used to adjust which ever mode you
have chosen for the AUX function.
PORT
• The genalert on setpoint functions are typically used
23.0vdc
with grid-interactive FXs. Press the <DOWN> soft
key three times to view the loadshed off setpoint
screen.
PORT
• The loadshed off setpoint is the battery voltage
which triggers the AUX to reduce the inverter and
battery loads. When the battery voltage drops below
22.0 vdc
this value for three seconds, the AUX powers a DC
coil relay to disconnect an AC load. Once triggered,
loadshed remains on for at least three minutes. The
PORT
loadshed off setpoint is adjustable from 20 VDC to
28 VDC in 0.1 VDC increments using the <INC> and
<DEC> soft keys. Press the <DOWN> soft key to
bring up the ventfan on setpoint.
• When the AUX is set to ventfan, a fan ventilates
a battery enclosure. The ventfan on setpoint
establishes the battery voltage which energizes the
13.0 vdc
AUX and thus the fan for a one minute period. The
voltage setting has a range of 20.0 VDC to 32.0 VDC
in 0.1 VDC increments using the <INC> and <DEC>
PORT
soft keys. Recharging causes batteries to emit mostly
hydrogen gas; higher recharging voltages emit more
gas. Press the <DOWN> soft key to view the ventfan
off period screen.
53