ADV/FX/AUX---------------P00
ventfan off
period
DOWN INC
ADV/FX/AUX---------------P00
diversion
on setpoint
DOWN INC
ADV/FX/AUX--------------P00
diversion
off delay
DOWN INC
54
5 min
DEC
PORT
14.6 vdc
DEC
PORT
30 sec
DEC
PORT
• If a ventilation fan is only needed intermittently,
the ventfan off period shuts the fan off for a user-
determined time before starting up again for a one-
minute period when the battery voltage exceeds
the ventfan on setpoint. This off period can be set
from 0-30 minutes in one-minute increments using
the <INC> and <DEC> soft keys. Setting this period
to zero will keep the fan running the entire time
the battery voltage is high enough to activate the
ventfan function. Setting it to five minutes means the
fan will run for one minute and then shut off for five
minutes until the battery voltage drops and the fan
is no longer needed. Press the <DOWN> soft key to
view the diversion on setpoint screen.
• After deciding on Divert DC or Divert AC, use the
diversion on setpoint screen to choose the voltage
which will activate this AUX OUTPUT FUNCTION.
This value can range from 24.0 VDC to 32.0 VDC and
can be adjusted in 0.1 VDC increments using the
<INC> and <DEC> soft keys. Press the <DOWN>
soft key to view the diversion off delay screen.
• The diversion off relay determines how long the AUX
will be energized after the battery voltage which
caused the diversion falls below the diversion on
setpoint. This delay can range from 0-240 seconds in
one-second increments as adjusted with the <INC>
and <DEC> soft keys.