7. Thermix split system (Fig. 2)
Heat exchanger
Number of plates
20
30
* maximum volumetric flow in the low temperature circuit
see Fig. 8 and 8.1
Requirements:
If the maximum power is secondarily consumed, no admixing happens so that the Thermix pump delivers the total volumetric flow via the heat
exchangers. The mixed heating circuit shows a pressure loss of 0.2 bar at the respective quoted maximum volumetric flow. The maximum
quoted volumetric flow corresponds to the adjusted pump level 3 of the Thermix pump.
see Fig. D2 and D2.1
19
max. V*
Power at 5K
[l/h]
[kW]
1040
5.93
1100
6.27
Fig. 8
A 3/4" MI connection - expansion tank
Fig. 8.1
A Bypass primary (see item 3.3) (needs to be closed in operational mode for proper functioning)
B Bypass secondary (see item 3.2)
C 3/4" Eurokonus
D Immersion sleeve
E Heat exchanger for number of plates, see table)
Fig. D2
A Volumetric flow – pressure loss diagram - Thermix seplit system primary side (heat exchanger)
B Pressure loss (bar)
C Volumetric flow [l/h]
Fig. D2.1
A FVolumetric flow – pressure loss diagram -Thermix split system secondary side
B Pressure loss (bar)
C FVolumetric flow [l/h]
Power at 10K
[kW]
11.86
12.54