GE LP Serie Manual De Instrucciones página 5

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 16
Safety instructions when working with battery
INTERNAL AND EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS
BY QUALIFIED SERVICE PERSONNEL.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING THE
UPS AND BATTERY.
Full voltage and current are always present at the battery terminals.
The battery used in this system can provide dangerous voltages, extremely high currents and a risk of electric shock.
If the terminals are shorted together or to ground they may cause severe injury.
You must be extremely careful to avoid electric shock and burns caused by contacting battery terminals or shorting
terminals during battery installation.
Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must install and service
the battery.
The installation must conform to national and local codes.
Keep unauthorised personnel away from the battery.
The qualified service person must take these precautions:
1
Wear protective clothing, such as rubber gloves and boots and protective eye wear
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewellery.
Do not carry metal objects in your pockets where the objects can fall into the battery cabinet.
2
Tools must have insulated handles and must be insulated so that they will not short battery terminals.
Do not allow a tool to short between individual or separate battery terminals or to the cabinet or rack.
Do not lay tools or metal parts on top of the battery, and do not lay them where they could fall onto the battery
or into the cabinet.
3
Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery‟s terminals, the string of battery, or to the
cabinet or rack.
4
Align the cables on the battery terminals so that the cable lug will not contact any part of the cabinet or rack,
even if the battery is moved.
Keep the cable away from any sharp metal edges.
5
Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch them.
6
Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
7
To reduce the risk of fire or electric shock, install the battery in a temperature and humidity controlled indoor
area, free of contaminants.
8
Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the battery conductors.
9
Where conductors may be exposed to physical damage, protect the conductors in accordance with all
applicable codes.
10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and remove the battery fuses.
GE Consumer & Industrial SA refuses any responsibility in case
of non-observance, unauthorised alterations or improper use
of the delivered UPS.
Modifications reserved
GE_UPS_USR_XCE_LPS_SGS_STP_XXX_V080.docx
Critical Power
DANGER !
Page 5/49
UPS Safety Rules

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tle serieSg serieLp33 serieSitepro

Tabla de contenido