PHASE 6:
ESTIMATED CAPACITY
warning
IMPORTANT
Never change this value. Should this accidentally happen, refer to the related column on the table.
• The system exchange capacity is shown on the display in
kg CaCO3 removed before regeneration is needed.
• The value results from the system size and salt
consumption L-S-H.
• The capacity shown on the display results from standard
calculation conditions.
• Exchange capacity shows the system potentials and for
timer 740 it cannot be changed.
• In order to change exchange capacity on timer 760,
press SET to make the default capacity flash.
Use UP and DOWN to increase up to the desired capacity.
• Press SET to confirm the setting and move to the next
parameter.
• If you use timer 740, the programming is complete.
The timer will take you back to normal operating mode.
PHASE 7:
ENTER HARDNESS
(ONLY FOR TIMER 760 WITH VOLUMETRIC CONTROL)
• Enter the hardness of incoming raw water.
• The default hardness value is 350 mg (35 French degrees °F)
• To change hardness, press SET in order to have the setting flash. Use UP and DOWN to increase/decrease the desired
hardness value.
• Press SET to confirm.
• The programmer will take you to normal operating mode.
warning
IMPORTANT
If the display shows fixed values "1.01-1.02-1.03", blow air inside the turbine for a few seconds to restart the programmer.
8