5.3 D15SH
The valve is available in the following sizes: 2", 2
• standard
- not available
Flanges:
PN25, ISO 7005-2, EN 1092-2, face to face length acc. EN 558-1
Housing:
Ductile cast iron (EN-GJS-400-15 EN 1563), coated with PA
(polyamide)
Note:
... = space holder for connection size
Note:
Ordering number example for DN50 and type B valve: D15SH-50B
5.4 D15SI
The valve is available in the following sizes: 2
• standard
- not available
Flanges:
PN16, ISO 7005-2, EN 1092-2, face to face length acc. EN 558-1
Housing:
Ductile cast iron (EN-GJS-400-15 EN 1563), coated with PA
(polyamide)
Note:
... = space holder for connection size
Note:
Ordering number example for 2
6
Assembly
6.1 Installation Guidelines
Install in horizontal pipework with spring bonnet
directed upwards
Installation in vertical pipework possible with increased
maintenance effort
Install shut-off valves
The installation location should be protected against
frost and be easily accessible
Pressure gauge can be read off easily
Simplified maintenance and cleaning
Install downstream of the filter or strainer
This position ensures optimum protection for the
pressure reducing valve against dirt
Provide a straight section of pipework of at least five
times the nominal valve size after the pressure reducing
valve (in accordance with EN 806-2)
Requires regular maintenance in accordance with
EN 806-5
6.2 Assembly instructions
1.
Thoroughly flush pipework
2.
Install pressure reducing valve
Note flow direction
Install without tension or bending stresses
3.
Seal in pressure gauges
GB
1
/
", 3" and 4".
2
1
/
", 3" and 4".
2
1
/
" and type A valve: D15SI-65A
2
7
7.1 Setting outlet pressure
1.
2.
3.
4.
5.
6.
7.
8.
9.
8
In accordance with EN 806-5, the following measures must
be taken:
4
Start-up
CAUTION!
Set outlet pressure 1 bar minimum under inlet
pressure
Close shut-off valve on inlet
Release pressure on outlet side (e.g. through water tap)
Close shut-off valve on outlet
Loosen hexagon nut on spring bonnet
Slacken tension in compression spring
Slowly open shut-off valve on inlet
Rotate adjustment screw, until the pressure gauge
shows the desired value
Retighten hexagon nut
Slowly open shut-off valve on outlet
Maintenance
We recommend taking out a servicing contract with an
installation firm
D15SH-...B