UV100A ULTRAVIOLET SYSTEMS
SPECIFICATIONS
IMPORTANT
The specifications in this publication do not include
normal manufacturing tolerances; therefore, an
individual unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions and some
minor differences in performance can be expected
if those conditions are changed.
Models available:
The UV100A Ultraviolet System is available in four models:
a single-lamp air treatment system; a dual-lamp air
treatment system; a 120V surface treatment system; and a
240V surface treatment system.
• UV100A Air Treatment System (single-lamp) is mounted
in the return air duct of an HVAC system. It has
moderate-efficiency performance against airborne
bacteria in return air applications.
• UV100A AIr Treatment System (dual-lamp) is mounted
in the return air duct of an HVAC system. It has high-
efficiency performance against airborne bacteria in
return air applications.
• UV100A Surface Treatment System (120V or 240V) is
mounted downstream from air conditioner cooling coils
of HVAC system. The unit reduces mold growth and
spores on duct surfaces, coils and drip pans. (Optionally,
UV100A Surface Treatment System can be mounted in
return air duct of HVAC system. It has moderate
efficiency per-forming against airborne bacteria in
return air applications.)
Efficiencies:
• UV100A Surface Treatment System (120V and 240V):
Kills up to 99.9% of mold on system cooling coils or kills
up to 75% of airborne bacteria passing by the system
(depending on installation).
—
Test performed in a test duct showed reduction in
colony-forming aspergillus niger mold spores when
surface was irradiated at a distance of 18 in. for
three hours in still air, using new lamps.
—
Test showed single-pass kill-rate of serratia bacteria
in a clean metal 12 in. x 25 in. duct at an airflow of
2000 cfm using new lamps.
• UV100A Air Treatment System (dual-lamp): Kills up to
87% of airborne bacteria passing by the system.
—
Test showed single-pass kill-rate of serratia
marcescens bacteria in a clean metal 12 in. x 25 in.
duct at an airflow rate of 2000 cfm using new
lamps.
68-0248ES—01
• UV100A Air Treatment System (single lamp): Kills up to
70% of airborne bacteria passing by the system.
—
Test showed single-pass kill-rate of serratia
marcescens bacteria in a clean metal 12 in. x 25 in.
duct at an airflow rate of 2000 cfm using new
lamps.
Electrical Ratings:
Power Rating: 120 Vac, 60 Hz or 240V, 60 Hz.
Consumption:
Model
UV100A1000 Air
Treatment System (single
lamp)
UV100A1018 Air
Treatment System (dual
lamp)
UV100A1059 Surface
Treatment System (120V)
UV100A2008 Surface
Treatment System (240V)
Temperature Ratings:
Air Treatment System (dual lamp):
Ambient Temperature Range: 30°F to 104°F (-2°C to
40°C).
Lamp Temperature Range: 30°F to 104°F (-2°C to 40°C)
and 170°F (77°C) in moving air.
Air Treatment System (single lamp) and Surface Treatment
System:
Ambient Temperature Range: 30°F to 120°F (-2°C to
49°C) and 170°F (77°C) in moving air.
Lamp Temperature Range: 30°F to 120°F (-2°C to 49°C)
and 170°F (77°C) in moving air.
Relative Humidity:
Up to 95% rh, non-condensing.
Dimensions: See Fig. 3.
Approvals:
Underwriters Laboratories: File no. E223009
The health aspects associated with the use of this product
and its ability to aid in disinfection of environmental air
have not been investigated by UL.
2
Input
Bulb
Voltage
Power
Wattage
(Vac)
(A)
(W)
120
0.4
18
120
0.7
36
(each bulb)
120
0.75
36
240
0.35
36