UV100A ULTRAVIOLET SYSTEMS
Surface Treatment System
When installed next to the cooling coil, the Ultraviolet
Surface Treatment System prevents a high percentage of
the growth of micro-organisms such as mold that may
grow on duct surfaces, coils and drain pans. Individual
results depend on careful installation and maintenance.
See. Fig. 2.
Fig. 2. Typical Surface Treatment installations.
IMPORTANT
If mounting options are limited, protect plastic or
rubber materials listed in CAUTION with ultraviolet-
resistant material such as aluminum foil duct tape.
68-0248ES—01
SE ME
NT
ER TIS
IN G/ AV
et les
WA RN
nu e
dre
pe au
mp ren
!
ur la
n co
an ce
.
int en
s po
et bie
No cif
lez lire
la ma
Ve uil
n et
lla tio
l'in sta
NT
SE ME
ER TIS
ING /AV
WA RN
et les
u nue
e
!
la pea
pre ndr
pou r
n com
ce.
et bie
inte nan
No cifs
ez lire
et la ma
Ve uill
llat ion
l'in sta
M22859
NOTE: When the installer is uncertain about whether the
drip pan in the installation can tolerate UV expo-
sure, consult the UV exposure white paper. This is
found by doing a search under the "technical liter-
ature" category for form no. 50-8788, at cus-
tomer.resideo.com.
1. The UV System can be mounted in any orientation.
2. Choose a location that is readily accessible for regu-
lar inspection and cleaning.
3. Allow clearance in front of the device for removing the
bulb assemblies. See Fig. 3 for bulb assembly
lengths.
4. Mount the UV System to non-lined metal ductwork.
Do not mount in a location that permits ultraviolet
exposure to plastic flexible duct liner.
CAUTION
Sharp Edges Hazard.
Can cause personal injury.
Be careful when inserting ultraviolet device into the
sheet metal cutout.
Wear protective gloves when working near sheet
metal.
Duct Mounting
Use the following instructions to mount the UV System on
the air duct of an HVAC system:
1. Disconnect power to the HVAC system before install-
ing the UV System.
2. Determine the location for installation (see Fig. 1 and
2):
a. The UV Air Treatment System requires an easily-
accessible, flat mounting surface on the metal
return air duct of the HVAC system. The UV Sur-
face
Treatment System requires an easily-accessible,
flat mounting surface on the metal supply air
duct of the HVAC system. The UV Surface Treat-
ment System must be located so the lamp sur-
rounds the evaporator coil and drip pan with
ultraviolet light.
b. The duct mounting location must be a minimum
of 8 in. wide. See Fig. 3.
c. The depth of the duct must accommodate the full
length of the ultraviolet bulb for your model as
shown in Fig. 3.
d. The unit should be located as far away as possible
from any rubber or plastic components, such as
isolators, in the duct.
e. The space adjacent to the mounting location
must be large enough to allow for ultraviolet bulb
installation and removal.
f.
A 120V or 240V electrical outlet must be within
range of the unit to plug in the power cord.
4