Honeywell 50022037-005 Instrucciones Para La Instalación página 2

Módulo para agua caliente doméstica
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

DOMESTIC HOT WATER MODULE
COLD
WATER
INLET
BOILER
SUPPLY
WATER
INDIRECT
WATER
HEATER
BOILER
RETURN
WATER
Fig. 1. Installing the 32003971-003 Temperature
WIRING
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large
inductive loads such as motors, line starters,
lighting ballasts and large power distribution
panels.
Use shielded cable to reduce interference when
rerouting is not possible.
1. Wire the EnviraCOM bus terminals 1,2, and 3 on
the DHW Module to the 1,2, and 3 terminals on the
EnviraCOM
enabled Aquastat, thermostat (if
available), or anywhere on the bus where access is
available and convenient. (See Fig. 2).
2. Connect the two 32003971-003 Temperature Sen-
sor wires to the TS terminals on the DHW Module.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
HOT WATER
SUPPLY PIPE
(SHOWERS,
SINK, ETC.)
32003971-003
SENSOR
M29650
Sensor.
NOTE: Shielded cable may be required if routing the
Temperature Sensor wires near/along high volt-
age lines, motors or other electrical noise-gen-
erating devices. Do not extend EnviraCOM
cabling beyond 1000 feet. Signal degradation
may occur.
3. See C7089U Installation Instructions (Form Num-
ber 69-1709EFS) for additional sensor installation
instructions and specifications.
2-13/32
(61)
EnviraCOM
Fig. 2. 50022037-005 Domestic Hot Water (DHW)
OPERATION
General
The 50022037-005 Domestic Hot Water Module is a
device which, when connected to an AquaReset enabled
Electronic Aquastat with a 50022037-002 Outdoor Reset
Module via the EnviraCOM
enables the control to prioritize a domestic hot water
demand. The Aquastat resets the present boiler
temperature setpoint to the High Limit in order to ensure
hot water for domestic use is available. Once the
domestic hot water demand is satisfied, the DHW
Module directs the Aquastat to reset the boiler
temperature setpoint to once again follow the outdoor
reset curve.
® U.S. Registered Trademark
© 2009 Honeywell International Inc.
69-2343EFS—01
M.S. 11-09
Printed in U.S.A.
2-29/32
(74)
2-13/32
(61)
Domestic Hot Water Module
50022037-005
EnviraCOM
Enabled
C
O
1 2
3 TS TS
M
1
2
3
L7224/L7248
AQUASTAT
Module wiring diagram.
communication bus,
3-25/64
(86)
32003971-003
SENSOR