Installation (continued)
4
Attaching tubes to the pump
□ Attach 3/8" clear vinyl tubing (2) to the check valve (1).
□ Secure with a 1/2" hose clamp (3) (not included).
□ Route the tubing up and away from the condensate pump (A).
□ Avoid compressing or kinking the tube.
NOTE: The tube route should be the shortest possible
distance from the pump to the building exterior or other
drain location. For best results, the distance that the water
must go UP should be shorter than the distance that it goes
DOWN.
NOTE: Check local codes for water discharge
requirements.
5
Installing the drain tubes
□ Install the condensate drain tubing (1) (not included) into
one of the four inlet holes (2), making sure the tubing is
straight.
NOTE: When using rigid tubing such as PVC, the bottom
should be cut to a 45º angle.
1
2
6
Install a "P" trap
□
If installing to a condensing furnace or humidifier, a "P" trap
(not included) should be used. This will prevent air or incidental
steam contact with the pump as this pump is UL rated for
temperatures only up to 140ºF.
"P" trap
Condensate
drain tubing
6
2
3
A
1
To condensing
furnace or humidifier
To Condensate pump (A)