3. Press both keys to resume programming at
point 4.2.3 (1), SiGn see A
⇑
⇑
4. When outputting the setpoint in Auto mode, when
the SPecial disPlay function is activated, the whole
current or voltage ranges are used.
I.e. the setpoint ranges 0...24 mA and 0...12 V
relate respectively to the scaled values.
If e.g. the value 5 is set for di.Lo and the value 10 is
set for di.Hi, the current output will be set as follows:
di.Lo 5 corresponds to 0 mA,
di.Hi 10 corresponds to 24 mA.
The scaled values must be used when inputting the
reference points (ou.1, ou.2, ...). If the reference point
ou.1 is to output 12 mA (in the above example), you
must input 7.5 and not 12 mA.
4.2.4 Example of Auto Operating Mode
Without Special display function
8 V
PE. 4
ou. 4
3 V
2 V
10 s 20 s 30 s 40 s 50 s
For a ramp, the number of steps and the height of the
steps depend on the programmed ramp time and on
the ramp height, step width is always fixedly program-
med at 0.1 sec. E. g.: For a 0-3V ramp in 5 s, a step
has a step height of 0.06V in 50 steps of 0.1sec.
in the flow chart
PE. 5
ou. 5
The best way to program such a function is to set up
a table like the one opposite:
Example
PEr
8
ou. 1
0 V
PE. 1
5 s
ou. 2
3 V
PE. 2
5 s
ou. 3
2 V
PE. 3
10 s
ou. 4
3 V
PE. 4
10 s
ou. 5
3 V
PE. 5
10 s
ou. 6
8 V
PE. 6
10 s
ou. 7
8 V
PE. 7
10 s
ou. 8
0 v
PE. 8
5 s
5. Technical Data
Display:
4-digit red 7-segment LED display,
height 8 mm
Supply voltage: 10...30 V DC, electrically isolated
Current consumption:
39 mA at 25°C, for a 20 mA output
current at 24 V DC
Power consumption:
max. 1 W
Test voltage:
500 V, 50 Hz., 1 min.
Test voltages:
EN 61010-1 for pollution level 2 and
overvoltage category 2
EMC:
EN 55011 Class B
EN 61000-6-2, EN 61000-6-3
EN 61326-1
Operating temp.: -20...+65 °C, without condensation
Storage temp.:
-25...+85 °C, without condensation
Air humidity:
90 % at 25 °C, without condensation
Protection:
IP65 (front side)
Weight:
approximately 50 g
Own values
EN - Page 8