Faults - WIKA GDM-100 Manual De Instrucciones

Ocultar thumbs Ver también para GDM-100:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. Commissioning, operation / 6. Faults
5.3 Switch point setting
The switch points have a fixed setting as standard and cannot be adjusted. Thus, an
undesired adjustment of the switch points is excluded.
EN
With customer-specific, adjustable switch points, with the accompanying adjustment
key, the desired set point can be set via the adjustment lock in the window.

6. Faults

Faults
Contact is no longer
switching in accordance
with the specification
16
CAUTION!
Physical injuries and damage to property and the environment
If faults cannot be eliminated by means of the listed measures, the
instrument must be taken out of operation immediately.
Ensure that pressure or signal is no longer present and protect against
accidental commissioning.
Contact the manufacturer.
If a return is needed, please follow the instructions given in chapter 9.2
"Return".
For contact details see chapter 1 "General information" or the back page
of the operating instructions.
Causes
Electrical connection is
interrupted
Electrical load unsuitable for
the switch contact model
Contact contaminated
WIKA operating instructions gas density monitor model GDM-100
Measures
Carry out a continuity test on the
electrical connection leads
Maintain the permissible
electrical loads for the switch
contact model