Toshiba TOSVERT VF-AS3 Manual De Inicio Rápido página 8

Ocultar thumbs Ver también para TOSVERT VF-AS3:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
Wire size for ND rating
Voltage
class
3-phase
240V
EN
6
6
6
Be sure to replace the covers removed during wiring.
5.
Turn on the power supply
Set the setup menu (Region setting) after first power on.
The procedures in this section is not necessary for subsequent power on.
6
WARNING
Main region
6
Motor
Max. frequency (FH)
6
(1) Turn the power on.
Setup menu is displayed.
6
6
Power circuit (mm
Applicable
motor (kW)
Input
Output
0.75
1.5
1.5
1.5
1.5
1.5
2.2
1.5
1.5
4.0
2.5
4
5.5
4
6
7.5
6
10
11
10
16
15
16
25
18.5
25
35
22
35
50
30
50
70
37
70
95
45
95
120
55
70x2
150
75
95x2
95x2
Set a region correctly. If the setting is incorrect, the drive will not work and some damage or
unexpected movement will happen.
Mainly North
America
230/460 (V)
60 (Hz)
80 (Hz)
STOP
SEt
:Region Setting check
0: Setup menu starting
1: Japan
2: Mainly North America
3: Mainly Asia
4: Mainly Europe
2
)
Grounding
Voltage
2
class
wire (mm
)
3-phase
2.5
480V
2.5
2.5
4
6
10
16
16
16
25
35
50
70
95
120
Mainly Asia
Mainly Europe
230/400 (V)
230/400 (V)
50 (Hz)
80 (Hz)
(2) Rotate the touch wheel to select a region.
1: Japan
2: Mainly North America
3: Mainly Asia
0.0Hz
02:39
4: Mainly Europe
5: China
EN-6
Power circuit (mm
Applicable
motor (kW)
Input
0.75-4.0
1.5
5.5
1.5
7.5
2.5
11
4
15
6
18.5
10
22
10
30
16
37
25
45
35
55
50
75
70
90
95
110
50x2
132
70x2
160
95x2
220, 250
150x2
280
150x3
315
150x3
China
200/380 (V)
50 (Hz)
50 (Hz)
80 (Hz)
50 (Hz)
STOP
Region Setup Mode
1: Japan
2: Mainly North America
3: Mainly Asia
4: Mainly Europe
E6582071
2
)
Grounding
2
wire (mm
)
Output
1.5
2.5
2.5
2.5
4
2.5
6
4
10
10
10
10
16
16
25
16
35
16
35
16
50
25
95
50
120
70
50x2
95
70x2
95
95x2
120
150x2
150
120x3
120x2
150x3
120x2
Japan
200/400 (V)
60 (Hz)
80 (Hz)
0.0Hz
02:40