En54-16: 2008 Compliancy Checklist - Bosch Praesideo 4.3 Manual De Uso

Sistema de megafonía y sistema acústico de emergencia
Tabla de contenido

Publicidad

Praesideo 4.3

EN54-16: 2008 compliancy checklist

Clause / Requirement
4 General requirements
4. 1 General
4. 1 . 1 If an optional function with requirements is
included in the VACIE, then all the corresponding
requirements shall be met (see Annex B).
4. 1 .2 If functions other than those specified in this
European Standard are provided, they shall not
jeopardize compliance with any requirements of this
European Standard
4.2 Combined VACIE and CIE
When the VACIE and CIE are combined they may
share common indications, manual controls and
outputs (see Annex F). In this case, the following shall
apply:
a
single fault in the CIE shall not adversely affect
the mandatory functions of the VACIE;
b
indication(s) and manual control(s) of the voice
alarm condition shall be clearly identifiable, with
the exception of the optional audible warning.
Bosch Security Systems B.V.
Compliance
Praesideo is compliant.
The following optional functions, with requirements, are included
in Praesideo from version 3.3 upwards:
Audible warning (7.3)
Phased evacuation (7.5)
Manual silencing of the voice alarm condition (7.6.2)
Manual reset of the voice alarm condition (7.7.2)
Output to fire alarm devices (7.8)
Voice alarm condition output (7.9)
Indication of faults related to the transmission path to the
CIE (8.3)
Indication of fault related to voice alarm zones (8.4)
Voice alarm manual control (10)
Interface to external control device(s) (11)
Emergency microphone(s) (12)
Redundant power amplifiers (13. 1 4)
The following optional functions with requirements are not
included in Praesideo:
Delay(s) to entering the voice alarm condition (7.4)
Disabled condition (9)
Praesideo power amplifiers and basic amplifiers shall not be
configured to enter the power save mode when mains power
fails. Although this would save battery power, the amplifier
supervision and line/loudspeaker supervision is not active in this
mode, which is a necessity for systems operating in accordance
with EN54-16.
The Praesideo PC call station shall not be used as an emergency
call station in systems operating in accordance to EN54-16. A
PC does not comply with the requirements as set forward by this
standard.
This requirement is not applicable. In Praesideo, the Voice Alarm
Control and Indicating Equipment (VACIE) is not combined with
a fire alarm Control and Indicating Equipment (CIE).