Installation and Maintenance Instructions
This section has wiring instructions for the flameproof models G-SND 24 Vdc,
120 Vac, 220-240 Vac.
Ex d units are supplied with an eleven-position PCB mounted screw terminal
block. The maximum wire gauge is 4 mm
(12 AWG). The wire must be rated
2
85 °C or higher. Use only stranded cable to terminate the sounder. The cross-
sectional area of the primary earth (ground) must equal the cross-sectional area
of the phase conductor.
Cable termination for these models should be in accordance with specifications
applying to the application. It is recommended that all cables and cores should
be fully identified. Use the appropriate cable gland for the application. Gland
entry threads are M20-1.5 x 6H.