Safety Information; Water Temperature - Bradley S19-120 Manual Del Usuario

Ducha de alto flujo de suministro horizontal con cabezal rociador de plástico. ducha de alto flujo de suministro horizontal con cabezal rociador de plástico y conjunto de cubierta
Ocultar thumbs Ver también para S19-120:
Tabla de contenido

Publicidad

Installation

Safety Information

To ensure proper operation:
Installation
This fixture has been designed and 3rd party tested to meet ANSI/ISEA Z358.1. The system must be tested periodically to be
sure it is functioning properly to meet the standard. Please refer to the ANSI/ISEA Z358.1 standard on testing requirements.
The installation, maintenance, and location of all safety drench showers, eye, and eye/face washes must comply with the
requirements of ANSI/ISEA Z358.1. Workers who may come in contact with potentially hazardous materials should be trained
regarding the location and proper operation of emergency equipment per ANSI/ISEA Z358.1.
ANSI/ISEA Z358.1 requires this unit to be used with a clean, potable, uninterrupted supply of tepid water. Bradley plumbed
emergency fixtures require a minimum of 30 psi flowing pressure in order to function as designed and meet the ANSI/ISEA Z358.1
standard.
Before installation make sure that this equipment will meet the requirements of the potential hazardous contaminants in your
location.
Installation of this system must be completed by a qualified plumber in compliance with all national and local codes. Compliance
and conformity to drain requirements and other local codes and ordinances is the responsibility of the installer.
Weekly Inspections
To ensure all emergency shower and eye/face wash fixtures are ready to be used when needed, regular checks and maintenance
must be conducted. Weekly inspections must be conducted on all safety equipment to make sure a suitable flushing fluid supply is
present and to make sure the equipment is in good operating condition.

Water Temperature

ANSI/ISEA Z358.1 requires tepid water. Suitable range is 60°F to 100°F (16°C to 38°C). Personal injury is possible outside this
temperature range.
Bradley • 215-148 Rev. B: ECO 19-05-034A
2/15/2021
S19-120, S19-120A