Configuration

Settable parameters:
- Running pressure.
When the pressure in the
system falls below the Pm,
PRESFLO
starts-up the pump.
®
The Pm should always be
higher by at least 0.2 – 0.3
bar of the pressure genera-
ted by the column of water
overlooking PRESFLO
.
®
The Pm value can be carried
in the field between 1 bar and
5 bar.
- Maximum current
allowed.
PRESFLO
is fitted with a cur-
®
rent sensor, which continually
detects the absorption of the
pump. If the current remains
above the set Imax value for
a significant period of time,
PRESFLO
stops the pump to
®
protect it from damages (LOCK
condition for OVERCURRENT).
PRESFLO
nevertheless allows
®
the Imax to be exceeded for
short periods during the pump
start-up phase.
For correct functioning,
the Imax should be set at
a value higher by approx.
10 – 20% to the maximum
absorption of the pump
(normally indicated on the
rating plate of the motor).
If this rating value is not known,
it s better to leave the standard
Imax value (16A) to avoid that
the pump stops also in normal
absorption conditions.
The Imax value may be varied
in the field between 4A and
16A.
Disposal
When disposing of any
PRESFLO
parts, adhere
®
to the relevant laws and
regulations in force in
the country in which the
equipment is being used.
Do not dispose of any
polluting parts in
the environment.
Manufacturer's setting:
PRESFLO
is supplied with the
®
following STANDARD CONFIGU-
RATION:
- Running pressure
Pm = 2 ( bar )
- Max. current allowed
I max = 16 ( A )
Configuration
The adjustment of the starting
pressure (Pm) and the ma-
ximum permissible current (I
max) is done by means of two
trimmers shown in FIG.
Statement of Compliance: we declare, under our own respon-
sibility, that the product in question is in compliance with the fol-
lowing European Directives and national implementation provisions
2014/35/CE Low Voltage Directive
2011/65/CE (RoHS)
2012/19/CE - 2003/108/CEE (WEEE)
2014/30/CE Electromagnetic Compati-
bility Directive (EMC)
EN 60730-2-6
EN 61000 6-3
1. Remove the small screwdri-
ver and adjust the trimmer on
the desired limits, according to
the values shown on the plate
located under the screwdriver.
2. The start-up pressure can
be adjusted continuously from
1 to 5 bar (trimmer A)
Bigarello 01.06.16
DGFLOW S.r.l.
President
Stefano Concini
3. The maximum permissible
current can be adjusted
continuously from 4 to 16 A
(trimmer B)
4. When you finish adjustment
close the cover
Made in Italy by
DGFLOW srl Via Emilia, 5
46030 Bigarello (Mantova) Italy
tel. +39 0376 340922
fax. +39 0376 249525
info@dgflow.it - www.dgflow.it

Publicidad

Tabla de contenido
loading

Productos relacionados para DGFLOW PRESFLO MULTI

Este manual también es adecuado para:

V00103101

Tabla de contenido