LF ELETTRONIC Manual De Instrucciones página 24

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Water softener ELETTRONIC with AUTOTROL digital head logix
Phase 4b: Set the safety regeneration mode
(only for programmers 760 with volumetric control)
IMPORTANT
Legislative Decree 443/90 establishes the obligation for automatic regeneration at least once
every 4 days.
• If you use 740, move to phase 5.
• Set the number of days for safety regeneration frequency
also without completing the cycle.
• Days "0" is the default value.
• The days can be set starting from ½ day (0.5) to 99 days.
• To change, press SET in order to have the value "0" flash.
• Use buttons UP and DOWN to change the number of days.
• Press SET to confirm the regeneration frequency and move
to the next cycle.
Phase 5: Set quantity of salt
IMPORTANT
Never change this value.
Should this accidentally happen, refer to the related column on the table.
• Set the desired regenerating quantity of salt.
• The default value is "S" , medium level.
• 3 levels of salt are available:
L – low level;
S – medium level;
H – high level;
• Choose the level that is more appropriate for the softener model.
• To change salt setting, press SET and use UP and DOWN to select the desired setting.
• Press SET to confirm the setting and move to the next parameter.
Set low salt quantity
22
(regenerating agent quantity)
Set salt standard quality
Set high salt quantity

Publicidad

Tabla de contenido
loading

Tabla de contenido