FoF Fan OFF time: (0÷15 min) with Fnc = C_n or C_y, (fan activated
in parallel with compressor). it sets the evaporator fan off cycling
time when the compressor is off. With Fon =0 and FoF ≠ 0 the
fan are always off, with Fon=0 and FoF =0 the fan are always
off.
ALARMS
ALC Temperature alarms configuration: (Ab; rE) Ab= absolute
temperature: alarm temperature is given by the ALL or ALU
values. rE = temperature alarms are referred to the set point.
Temperature alarm is enabled when the temperature exceeds
the "SET+ALU" or "SET-ALL" values.
ALU MAXIMUM temperature alarm: (SET÷110°C) when this
temperature is reached the alarm is enabled, after the "ALd"
delay time.
ALL Minimum temperature alarm: (-50.0÷SET°C) when this
temperature is reached the alarm is enabled, after the "ALd"
delay time.
ALd Temperature alarm delay: (0÷255 min) time interval between
the detection of an alarm condition and alarm signalling.
dAO Exclusion of temperature alarm at startup: (from 0.0 min to
24h) time interval between the detection of the temperature
alarm condition after instrument power on and alarm signalling.
RELAY CONFIGURATION
oA1 Relay 9-10 configuration: dEF= defrost;
ALr= alarm; LiG= light; AUS= do not select it; OnF= on /off;
db= neutral zone; CP2= do not select it; dF2= do not select it.
oA2 Relay 11-12 configuration: dEF= defrost;
ALr= alarm; LiG= light; AUS= do not select it; OnF= on /off;
db= neutral zone; CP2= do not select it; dF2 = do not select
it.
OTHER
dP2 Evaporator probe display.
rEL Software release for internal use.
Ptb Parameter table code: readable only.
7. INSTALLATION AND MOUNTING
Instruments XW20LS/XW30LS shall be mounted on vertical panel, in
a 150x31 mm hole, and fixed using two screws
an IP65 protection grade use the front panel rubber gasket (mod. RG-
L, optional).
8. ELECTRICAL CONNECTIONS
Relays and power supply have a Faston connection (6,3mm). Probes
have a Faston connection of 2.8mm.
9. HOW TO USE THE HOT KEY
9.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT
(UPLOAD)
1.
Program one controller with the front keypad.
When the controller is ON, insert the "Hot key" and push
2.
key; the "uPL" message appears followed a by flashing "End"
Push "SET" key and the End will stop flashing.
3.
4.
Turn OFF the instrument remove the "Hot Key", then turn it ON
again.
NOTE: the "Err" message is displayed for failed programming. In this
case push again
o
o o
o
key if you want to restart the upload again or
remove the "Hot key" to abort the operation.
9.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a programmed "Hot Key" into the 5 PIN receptacle
and then turn the Controller ON.
1598018305 XW20LS-XW30LS IRD IT-GB-FR-TD-ES r1.0 10.01.2008
Manual GB
FAn= fans;
FAn= fans;
3 x 2mm. To obtain
∅
o
o
o o
XW20LS - XW30LS
3.
Automatically the parameter list of the "Hot Key" is downloaded
into the Controller memory, the "doL" message is blinking
followed a by flashing "End".
4.
After 10 seconds the instrument will restart working with the new
parameters.
5.
Remove the "Hot Key".
NOTE the message "Err" is displayed for failed programming. In this
case turn the unit off and then on if you want to restart the download
again or remove the "Hot key" to abort the operation.
10. ALARM RECOVERY
(Ref. Tab.4) Probe alarms "P1", "P2", start some seconds after the
fault in the related probe; they automatically stop some seconds after
the probe restarts normal operation.
Temperature alarms "HA", "LA" automatically stop as soon as the
temperature returns to normal values.
11. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XW20LS/XW30LS facia 38x185 mm; depth 48mm
Mounting: XW20LS/XW30LS panel mounting in a 150x31 mm panel
cut-out with two screws.
3 x 2mm. Distance between the holes
∅
165mm
Protection: IP65.
Frontal protection XW20LS/XW30LS: IP65 with optional frontal
gasket mod; RG-L.
Connections: XW20LS/XW30LS: Heat-resistant cable 2,8mm
Faston and heat-resistant cable 6,3mm Faston (230Vac).
Power supply: 230Vac ± 10%, 50/60Hz or 120Vac ± 10%, 50/60Hz
Power absorption: 3VA max
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 2 NTC probes.
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
oA1(9-10): (not for XW20LS) relay SPST 8(3) A, 250Vac
oA2(11-12): relay SPST 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal.
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20÷85% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C
(-58÷230°F).
Resolution: 0,1 ° or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit.
1598018305