LED unit 170VS
Electric installations
Bear in mind local electrical codes for switch box location.
The light shall always be connected via a safety transformer 12V AC of toirodal core-type (see table) to ensure correct operation
and maximum life. If more than one RGB light are installed, they shall be connected to the same transformer and via a common
power switch for synchronization, see Diagram.
The transformer's power shall be greater than the total value of all lights, please refer to the table below.
Supplied cable shall always be used for the engagement of the light.
If the light's external cable insulation or the inner conductor is damaged, it shall be replaced by a service technician or other
qualified person.
OBS! The lights should be completely covered by the water before they come on.
Recommendations
Option 1.
Cable length and cross-section, see table
Option 1
4m cable included in lamp package
Separate cable ( not included )
The colour of the light
WW
RGB - red/green/blue
Option 2
The colour of the light
WW
RGB - red/green/blue
The calculations of the cable lengths are made in relation to the maximum voltage drop in the electrical cables.
Wiring instructions Setup 1
Wiring instructions Setup 2
For new installations
For existing or other installations
Each lamp is connected to the transformer by a separate cable
All lamps are connected to the transformer via 1 cable
Cable included
4m cable included in lamp package
Separate cable not included
Separate cable ( not included )
8
!
Always use a toroïdal transformer
Maximum cable lenght / Cable section
1.5 mm
2.5 mm
2
2
10
50 m
85 m
20 m
35 m
Maximum cable lenght / Cable section
Quantity
2.5 mm
2
1
85 m
2
43 m
3
28 m
4
21 m
1
35 m
2
18 m
3
12 m
4
9 m
Option 2.
Cable length and cross-section, see table
!
4m cable included in lamp package
Separate cable ( not included )
4.0 mm
6.0 mm
10.0 mm
2
2
135 m
200 m
55 m
85 m
4.0 mm
6.0 mm
10.0 mm
2
2
135 m
200 m
68 m
100 m
45 m
67 m
34 m
50 m
55 m
85 m
28 m
43 m
18 m
28 m
14 m
21 m
8
ENGLISH
Always use a toroïdal transformer
This setup is not preferred for installations
!
where a PLP-REM(-300) is used
Transformer power
2
340 m
20VA
145 m
45VA
Transformer power
2
340 m
20VA
170 m
40VA
113 m
60VA
85 m
80VA
145 m
45VA
73 m
90VA
48 m
135VA
36 m
180VA