I/O Wiring Data
NOTICE
Specifications
Technische Daten
Spécifications
Specifiche
Electrical Specifications
Catalog No.
Voltage Range
Référence
Tension
Bestell-Nr.
Spannung
N. Catalogo
Tensione
Referencia
Voltaje
1492-IFM20F-F-2
0 - 132 V AC/DC
1492-RIFM20F-F-2
0 - 132 V AC/DC
1492-IFM20F-F24-2
10 - 30 V AC/DC
1492-RIFM20F-F24-2
10 - 30 V AC/DC
1492-IFM20F-F120-2
85 - 132 V AC/DC
1492-RIFM20F-F120-2
85 - 132 V AC/DC
1492-IFM20F-F240-2
168 - 264 V AC/DC
1492-IFM20F-F24A-2
10 - 30 V AC/DC
1492-RIFM20F-F24A-2
10 - 30 V AC/DC
1492-IFM20F-F120A-2
85 - 132 V AC/DC
1492-RIFM20F-F120A-2 85 - 132 V AC/DC
1492-IFM40F-F-2
0 - 132 V AC/DC
1492-IFM40F-F24-2
10 - 30 V AC/DC
1492-RIFM40F-F24-2
10 - 30 V AC/DC
1492-IFM40F-F120-2
85 - 132 V AC/DC
 For transients > 600 Vp use a UL recognized suppression device rated at 2.5 kV withstand.
7
Pour des transitoires > 600 Vp utilisez un dispositif de suppression certifié UL à 2,5 kV nominal de tenue.
Für Einschaltstöße > 600 Vp verwenden Sie einen UL anerkannten Entstörer, der bewertet wurde bei 2,5 kV standzuhalten.
Per transitori > 600 Vp usare dispositivo di soppressione riconosciuto da UL capace di sopportare 2,5 kV.
Para transitorios > 600 Vp use un dispositivo de supresión reconocido UL clasificado con 2,5 kV.
8
Power, input and output (I/O) wiring must be in accordance with Class I Division 2 wiring methods - Artticle 501-10(B)(1) of the National Ele
Explosion Hazard - substitution of components may impair suitability for Class I Division 2.
WARNING
Explosion Hazard - Do Not Disconnect Equipment unless power has been switched off or the area is known to be Non-Hazardous.
SURGE SUPPRESSION follow the literature recommendations of the PLC module being used.
La section SUPPRESSION DES SURTENSIONS se trouve à la suite de la littérature qui contient les recommandations relatives au module PLC utilisé.
ÜBERSPANNUNGSSCHUTZ Bitte beachten Sie die Dokumentationsempfehlungen für das jeweils benutzte SPS-Modul.
Per la SOPPRESSIONE DEI PICCHI TEMPORANEI, seguire le istruzioni riportate nella documentazione in dotazione al Modulo PLC utilizzato.
SUPRESIÓN DE SOBRETENSIÓN, siga las recomendaciones indicadas en la documentación del módulo PLC respectivo.
Reference Publications: Refer to 1770-4.1 and appropriate PLC I/O module installation manual.
PN-264488
DIR 10001268600 (Version 01)
Printed in U.S.A.
Wiring information for your I/O module, AIFM module and cable (e.g. wiring diagram and pinouts)are available online at www.rockwellautomation.com/en/e-tools.
To obtain information follow this procedure.
1) In the Catalog Number BOX at the above online site type in the catalog number of the IFM, AIFM, etc. module you are using and click on Submit.
2) At the next screen displayed, click on the Modify key (lower left of screen).
3) Click on the areas that indicate NO SELECTION and enter your specific configuration information (e.g. I/O platform, I/O MODULE, ETC.).
NOTE: To obtain the wiring diagram, you must select th Pre-Wired Cable Connector selection.
4) Configure your 1492 cable by filing in the NO SELECTION areas.
5) Click on the ACCEPT key for the configured 1492 cable. At the next screen click on ACCEPT for the 1492 module.
6) The next screen (Configuration Results) displays the results of your specific configuration. The "supplementary Documents" column contains I/O wiring information
for the configuration (e.g. I/O Wiring Diagrams). configuration (e.g. I/O Wiring Diagrams).
Especificaciones
Max. Current/Module
Max. Current/Circuit
Max. Courant/Module
Max. Courant/Circuit
Max. Strom/Modul
Max. Strom/Schaltkreis
Max. Corrente/modulo
Max. Corrente/circuito
Max. Intensidad/módulo
Max. Intensidad/circuito
2 Amps
12 Amps
0.5 Amps
4 Amps
2 Amps
12 Amps
Indicator Circuit Current
Maximum Recurring Peak Voltage
Courant circuit voyants
Tension de crele réurrente maximale
Strom, Anzeigeschaltkreis
Maximale periodische Hochstspannung
Corrente circuito indicatori
Tensione massima di cresta ricorrente
Intensidad del circuito
de indicadores
Voltaje de cresta iterativo máximo
N/A
N/A
2.0 mA
2.0 mA
2.5 mA
2.5 mA
< 1.5 mA
2.5 mA
2.5 mA
1.2 mA
1.2 mA
N/A
2.0 mA
2.0 mA
2.5 mA
PN-264488
7
Standards
Normes
Standards
Standard
Estándares
Temperature
cULus
Code at 60°C
600 V
Yes
p
8
CE
FM
T3C
Yes
Yes

Publicidad