12
UK
5 - ELECTRICAL CONNECTIONS: TERMINAL BOARDS
Terminal
Position
1
2
3
4
5
M1
6
7
8
9
10
M2
11
12
13
14
15
16
17
18
19
20
21
M3
22
23
24
25
26
27
28
M4
29
Signal
Description
Motor 1 connection (opening)
Motor 1 connection (common)
Motor 1 connection (closing)
Motor 2 connection (opening)
Motor 2 connection (common)
Motor 2 connection (closing)
COURTESY LIGHT output (PHASE) if DIP1_9 = OFF
Fixed output for FLASHLIGHT if DIP1_9 = ON
COURTESY LIGHT output (NEUTRAL) if DIP1_9 = OFF
Fixed output for FLASHLIGHT if DIP1_9 = ON
230VAC power supply NEUTRAL
N
L
230VAC power supply PHASE
Earth wire connection
EARTH
Earth wire connection
EARTH
COM
COMMON for LIMIT SWITCH, PHOTOCELL, STOP, START and PEDESTRIAN inputs
FCCM2
Closing limit switch input - MOTOR 2 (N.C.)
Opening limit switch input - MOTOR 2 (N.C.)
FCAM2
Closing limit switch input - MOTOR 1 (N.C.)
FCCM1
FCAM1
Opening limit switch input - MOTOR 1 (N.C.)
PHOTO
PHOTOCELL input (N.C.)
START input (N.O.)
START
24VAC output for PHOTOCELL, ACCESSORIES power supply (max 8W)
24Vac
0Vac
0VAC output for PHOTOCELL, ACCESSORIES and ELECTRIC LOCK power supply
EL1
12VAC output for ELECTRIC LOCK (max 15W)
STOP input if DIP2_1 in OFF - FRAME input if DIP2_1 in ON.
STOP
If not used, make a bridge with terminal 25 and open jumper SW15.
PEDESTRIAN start input (N.O.) - ACTS ON MOTOR 1.
PED
The pedestrian maneuver is made with automatic logic and cannot be modified.
COM
COMMON for LIMIT SWITCH, PHOTOCELL, STOP, START and PEDESTRIAN inputs
ANTENNA BRAID input
COM
ANTENNA CORE input
RELAY CLEAN-CONTACT FOR:
• Fixed-light flashlight connection taking the power supply from terminals 7 and 8
(the relay flashes fast during opening and slow during closing).
• Controlling a warning light to signal gate movement. Connect a 24VAC light powered
by terminals 20-21 (max 3W). The light flashes fast during opening, slow during
closing, it is on during pause and it is off during sleep time.
F4 PLUS