Rotating Field Testing (Max. 400 V); Continuity Testing; Fi/Rcd Trigger Test, Pe (Pe Conductor Test); Battery Replacement - Testboy Profi LED Plus Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 39

Rotating field testing (max. 400 V)

Determine which wires are the phase conductors, as described in the
"Phase testing" section. Now place two phase conductors on the test leads
and touch the finger contact. "<L" appears to indicate a counter-clockwise
field or "R>" for a clockwise field. The voltage display should show approxi-
mately 400 volts. If "<L" and only 230 volts are displayed, then only one
phase conductor is active.

Continuity testing

(Hold the test leads together in order to switch on.)
Touch the test leads onto the wire or fuse etc. that should be tested. At a re-
sistance of 0 - 500 kΩ the "Rx/Ω" LED lights and an acoustic signal sounds.

FI/RCD trigger test, PE (PE conductor test)

The Testboy
circuit breaker by means of two buttons (FI\RCD). The FI/RCD (max. 30 mA) is
tested between the phase and the PE conductor (max. 240 V).

Battery replacement

To replace the batteries, release battery compartment cover by turning it 90°
and pull downward to remove. Observe the correct polarity when inserting
the new batteries.
The positive terminals of the batteries have to show to the centre of the de-
vice. Do not use without battery cap!
Batteries should not be disposed of as normal household waste.
Take them to an approved collection point.
®
Testboy
Profi LED Plus
®
Profi LED Plus carries a load that enables it to trigger a FI/RCD
Operation
25

Publicidad

Tabla de contenido
loading

Tabla de contenido