2.0 - TECHNICAL DATA

• Use
• Ambient temperature (TS)
• Power supply voltage (DN 15 - DN 20 - DN 25)
• Power supply voltage (DN 32 - DN 40 - DN 50)
• Power supply tolerance
• Electric wiring
• Absorbed power
• Maximum operating pressure
• Protection rating
• Coil protection mode
• Mechanical strength
• Rp Threaded connections
• Flanged connections that can be coupled
to PN 16 flanges
• NPT threaded or ANSI 150 flanged connections : request feasibility
• In compliance with
*
Only single-phase, the device does not work if powered with three-phase voltage.
** DN 25 with swivel flanges.

2.1 - MODEL IDENTIFICATION

JVAP/NA
: DN 15 - 20 - 25
JVAP-1/NA : DN 15 - 20 - 25
JVAP-3/NA : DN 15 - 20 - 25
JVAP-6/NA : DN 15 - 20 - 25
JVA-1/NA
: DN 32 - 40 - 50
JVA-3/NA
: DN 32 - 40 - 50
JVA-6/NA
: DN 32 - 40 - 50

3.0 - COMMISSIONING THE DEVICE

3.1 - OPERATIONS PRIOR TO INSTALLATION

All installation operations must be carried out in the absence of an explosive atmosphere.
• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
If the device is threaded:
• make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
If the device is flanged:
• make sure the inlet and outlet counter-flanges are perfectly coaxial and parallel in order to prevent unnecessary
mechanical stress to the body. Also calculate the space to insert the seal gasket;
• With regard to tightening operations, equip yourself with one or two calibrated torque wrenches or other controlled locking tools;
Madas Technical Manual - 1|1.7J - REV. 0 of 1
: non-aggressive gases of the three families (dry gases)
: -20 ÷ +60°C
: 12 Vdc - 12 V/50 Hz - 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
: 24 Vdc - 24 V/50 Hz- 110 V/50-60 Hz - 230 V/50-60 Hz*
: -15% ... +10%
: electric cable l=3 metres with wire terminals
: see tables 2a - 2b - 2c
: 0.36 - 1 - 3 - 6 bar (see product label)
: IP65
: II 3G Ex mc ec nC IIA T4 Gc X - II 3D Ex mc tc IIIC T135°C Dc X
: Group 2
: (DN 15 - DN 20 - DN 25 - DN 32 - DN 40) according to EN 10226
: (DN 25** - DN 32 - DN 40 - DN 50) according to ISO 7005
: PED Directive 2014/68/EU (versions with max P. 1 - 3 - 6 bar)
EN 60079-0-7-14-15-18-31 - ATEX Directive 2014/34/EU
Directive EMC 2014/30/EU - Directive LVD 2014/35/EU
Directive RoHS II 2011/65/EU
max P. 360 mbar
ATEX 3G - 3D
max P. 1 bar
ATEX 3G - 3D
max P. 1 bar
ATEX 3G - 3D
max P. 6 bar
ATEX 3G - 3D
max P. 1 bar
ATEX 3G - 3D
max P. 3 bar
ATEX 3G - 3D
max P. 6 bar
ATEX 3G - 3D
11