LMF Clima LC2 Manual De Uso página 33

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Address
read Description Input-Output
State On-Off digital input (DI1)
8192
0 = Off; 1 = On
8960 Regulation Probe
External Damper
8961
0 = Off; 1 = On
8962 Current Return Fan Speed
8963 Current Supply Fan Speed
8964 Three Point Cold or Changeover Valve
Estimated Position
8965 Three Point Hot Valve Estimated Position
Pump 1 COLD OR CHANGE
8966
0 = Off; 1 = On
Pump 2 HOT
8967
0 = Off; 1 = On
Heater Status
8968
0 = Off; 1 = On
Pre Heater Status
8969
0 = Off; 1 = On
External Bypass Status
8970
0 = Off; 1 = On
8971 Outdoor Temperature
8975 Outlet Pressure
8976 Inlet Pressure
8977 CO2
8978 Expulsion Temperature
8979 Antifreeze Temperature
8987 On Off Status
8988 Boost Status
8989 Mixing Chamber Opening Status
Address
Description
read
Allarm
9000 Outlet Probe Error
9001 Outdoor Probe Error
9002 SKW Probe Error
9003 Filter Alarm
9004 Heater Alarm (Manual Reset)
9005 Inlet Pressure Probe Error
9006 Outlet Pressure Probe Error
9007 CO2 Probe Error
9008 Defrost/Expulsion Probe Error
9009 Inlet Fan Alarm (Manual Reset)
9010 Outlet Fan Alarm (Manual Reset)
9011 Antifreeze Probe Error
9012 Pre Heater Alarm (Manual Reset)
9013 Expansion Communication Alarm
9014 Antifreeze Alarm
9015 Fire Alarm (Manual Reset)
9016 Min Hot Water Temperature Alarm
9017 Clock Error
9018 SKW Probe AIR2 Error
9019 SKW Communication Alarm
Note:
(divided 10, °C) divide the value by 10, the result is in degree Celsius with one decimal place (Es: 175= 17.5°C)
(divided 10, %) divide the value by 10, the result is in percentage with one decimal place (Es: 505= 50.5%)
(HH:MM) minutes starting from midnight where 0= 00:00 e 1439= 23:59 (In example: 120= 02:00; 1170= 19:30)
firmware 1.03
Electronic Control "LC2" User Manual
Value
0
17.5
0
0.0
0.0
100.0
100.0
1
1
0
0
0
11.2
72
0
0
6.7
10.0
0
0
100.0
0= Not Active
1= Active
2=Manual Reset
Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Um
Default
Min
0
0
°C
0
-500
0
0
%
0
0
%
0
0
%
0
0
%
0
0
0
0
0
0
0
0
0
0
0
0
°C
0
-500
Pa
Pa
ppm
°C
-500
°C
-500
0
0
0
0
%
0
0
Um
Default
Min
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Rev.11
EN
Max
1
1100
1
1000
1000
1000
1000
1
1
1
1
1
1100
1100
1100
1
1
1000
Max
1
1
1
1
2
1
1
1
1
2
2
1
2
1
1
2
1
1
1
1
EN 15/ 15

Publicidad

Tabla de contenido
loading

Productos relacionados para LMF Clima LC2

Tabla de contenido