battery replacement
c see important battery safety rules
(see page i);
c batteries can be replaced without risk, but
don't hesitate to contact our after sales
department to confirm batteries failure, and
to give you further informations;
c battery replacement can be performed
UPS on utility power, but we recommend
C
you to switch off the unit in order to avoid
any data loss;
c grasp the top of the front panel and pull it
B
down (see drawings);
A
c fold front panel on the side or on top on of
the UPS, be careful not to damage the
ribbon cable from the UPS;
c use a screwdriver to remove screws on
metal front panel;
c pull out battery block using tapes on the
E
sides;
c disconnect battery wires red (+) and black
(-) coming from the UPS on battery
terminals;
c replace all battery block with new
batteries, same voltage and same rating
(Volts, Ah), then connect battery wires again
(sparks may happen during connection);
c push battery block in its location, screw
metal front panel, then click plastic front
panel.
D
28
Pulsar ESV +: E-51032616XT/AA
MGE UPS SYSTEMS