Disposal
Feature
Channels
Inactive channels are shown with a dotted selection field.
If the selected channels does not correspond to the number of required channels
for the group alarm group, the user is displayed a message regarding this.
Create a common alarm for a group of N channels with the relay configured as a
group alarm 1 of N and the corresponding channels defined in the group alarm
group.
The following settings are only required for common, single and group alarms.
Feature
Alarm type
Activation
mode
Latching
Acknowledge-
able
9
Disposal
10
Technical data
Versions with operating console (REGARD® 3900 and 3920)
Dimensions
Weight
Material
Degree of protection
Cable entry
All versions
Cable x-section
AC input voltage (to energy sup-
ply unit)
Description
Is only required for single or group alarms.
Single alarm - select channel from the channel list.
Group alarm - specifies how many channels of a group are
required to trigger the alarm: [Number of channels to trigger the
alarm] of [total number of channels in the alarm group]. Then
select the channels from the channel list.
Description
Selects the desired alarm or fault (A1, A2, A3, F1 or F2).
Selects whether the relay is activated during an alarm or acti-
vated in normal state.
Selects whether latching or non-latching.
Selects whether acknowledgeable or non-acknowledgeable.
This product must not be disposed of as household waste. This is indicated
by the adjacent symbol.
You can return this product to Dräger free of charge. For information please
contact the national marketing organizations or Dräger.
415 x 305 x 175 mm
approx. 5 kg
ABS-VO
IP65
M20 (qty 30)
2
Max. 2.5 mm
2
Min. 0.5 mm
Typical: 98 to 253 V AC, 50 to 60 Hz
®