Technical data
Type
Power supply
Nominal current
Nominal force
Nominal locking force
Lifetime
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Nominal stroke length*
Additional functions *
* Programmable with software SW-BSY+
Normal operation =
SHEV- fast running =
Forces
ZA 35
ZA 85
OPEN
300 N
800 N
CR III
300 N
800 N
CR II
300 N
800 N
CR I
300 N
800 N
Closing edge protection
In "CLOSE" direction the drive has an active
protection for the main closing edge. With an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then drive "CLOSE" again. If
after three attempts a closing is not possible, the
drive remains in this position.
In addition, the drive has a passive protection. The
closing speed in closure Range 2 and 1 is reduced to
5 mm/s.
Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.
8/20
ZA-BSY+
ZA35-BSY+(-HS)
ZA85-BSY+(-HS)
24 VDC, ±15%
24 VDC, ±15%
0,5 A (1,2 A)
1,0 A (2,0 A)
300 N
800 N
1100 N
>10 000 double strokes
30 % (With cycle time 10 minutes)
A
nodized aluminium / polycarbonate
IP 65
-5 ... +75°C
30 min / 300°C
S
ee type plate
C
losing edge protection activated (3 stroke repeatings)
ZA 105 ZA 155
1000 N
1500 N
1000 N
1000 N
All forces
1000 N
1000 N
+ approx. 20 % switch-off reserve
800 N
800 N
(temporary)
ZA105-BSY+(-HS)
24 VDC, ±15%
1,2 A (2,2 A)
1000 N
Running speed and forces
Main closing edge
English
ZA155-BSY+(-HS)
24 VDC, ±15%
1,4 A (2,5 A)
1500 N
99.824.31 1.2/03/12