!
Installation Guide
1
Electrical connections:
3
supply connectors;
Input connectors;
5
6
Status LED;
Resistor (alarm 2);
8
Resistor (standby).
D
ESCRIPTION
The KAL460 provides a remote input to an analogue fire detection
system. The input signal is constantly monitored and its status
communicated to the fire panel. The module has five possible
states: standby, open-circuit, short-circuit, alarm 1 and alarm 2.
The input does not have polarity and may be activated by closing
or opening a potential free contact (depending on the module
configuration).
The status LED is lit constantly during alarm.
I
NSTALLATION
For general guidelines on fire system planning,
design, installation, commissioning, use and
maintenance refer to the EN54-14 (2001) standard
and local regulations.
© 2005 GE Interlogix B.V.. All rights reserved.
Version 2-2 / July 2005
1052513
2
Loop connectors;
Auxiliary power
4
DIP Switches;
7
Resistor (alarm 1);
KAL460 Addressable Input Module
The module is designed for cabinet installation and must be
protected against environmental agents. The power supply should
be disconnected during installation.
The 24 V power supply can be taken from the loop or from an
auxiliary power source.
If more than 10 KAL400 series modules are connected to a loop,
an auxiliary power supply is recommended. Always verify large
installations using the loop load calculator to confirm that enough
power is available on the loop.
Power supply configuration
To set the module power supply remove the unit cover and
configure jumpers JMP1 and JMP2. See Figure 2: power supply
jumper configuration.
Figure 2: power supply jumper configuration
Loop powered.
24 VDC auxiliary power supply.
Installation Guide