General warning
Using this Quick Setup, you can carry out quick and
EMC-correct installation of the frequency converter
in five steps. The Operating Instructions, which are
also enclosed, give other examples of installation
and describe all functions in detail.
Read the safety instructions on the next
page before installing the unit.
Mechanical Installation
AKD 2800 frequency converters allow side-by-side
installation. Because of the need for cooling, there
must be 10 cm free air passage above and below
the frequency converter. Drill holes in accordance
with the measurements given in section Mechanical
dimensions. Retighten all four screws.
Fit the decoupling plate to the power cables and
the earth screw (terminal 95).
Electrical Installation, power
Please note that the power terminals can be removed.
Connect mains to the mains terminals of the frequency
converter, i.e. 91, 92, 93 and the earth connection to
terminal 95. Fit a screened/armoured cable from the
motor to the motor terminals of the frequency converter,
i.e. U, V, W. The screen ends in a screen connector.
MG.28.J1.62 - VLT is a registered Danfoss trademark
AKD 2800 Quick Setup
Electrical Installation, control cables
Remove the front cover underneath the control panel.
Place a jumper between terminals 12 and 27.
Programming
Carry out programming on the control panel. Press the
[QUICK MENU] key to enter the Quick menu. In this
menu, parameters can be selected by means of the [+]
and [-] keys. The parameter values can be changed by
pressing [CHANGE DATA]. Changes are programmed
using the [+] and [-] keys. Finish the change of a
parameter setting by pressing [CHANGE DATA]. A
change of parameter values is saved automatically after
a mains failure. If the display shows three dots at the
right, the parameter value has more than three digits.
In order to see the value, activate [CHANGE DATA].
Press [QUICK MENU]: Set the motor parameters
that are on the nameplate of the motor:
Motor power [kW]
Motor voltage [V]
Motor frequency [Hz]
Motor current [A]
Rated motor speed
Activate AMT:
Automatic motor tuning
Set reference range
Min. reference, Ref
MIN
Max. reference, Ref
MAX
Ramp-up time [s]
Ramp-down time [s]
In parameter 002 Local/remote control, the frequency
converter mode can be selected as Remote
parameter 102
parameter 103
parameter 104
parameter 105
parameter 106
parameter 107
parameter 204
parameter 205
parameter 207
parameter 208