The OFF delay for the contacts B
and D/B always apply jointly to both
outputs. If applicable, check by
repeating the function test.
Photoelectric light controller
setting
The sensitivity of the photoelectric
lighting controller can be steplessly
adjusted from appr. 2 Lux (night
time operation) to 300 Lux (daytime
operation).
13 On the right next to the hemi-
spherical sensor is the potentiometer
for setting the response threshold.
The extreme left-hand setting
is for night-time operation, the
Troubleshooting
Fault
No function
Does not switch on
Does not switch off
Continuously switches on/off
Switches on for no reason
extreme right-hand setting day-time
operation. The default setting of the
movement sensor module is for day-
light operation.
The sensitivity of contacts D and
D/B always applies jointly to both
outputs. The setting should ideally
be checked using output "D". As
this movement sensor module is
equipped with an integrated dazzle
protection, please note the fol
lowing:
Any change to the photoelectric
lighting controller setting can only
be checked after a delay of 60 sec
onds. This delay must be observed
after each change of the photoelec
tric lighting controller setting.
Cause
Fuse is defective
Short circuit
Not switched on
During daytime operation photoelec
tric switch threshold is too low
Bulb gone
Relay defective
Mains fuse defective
Relay switched to continuous light
Switched over to continuous light by
supplementary protective circuit
Continuous movement in pick-up
area
The activated lamp is located in the
pickup area
Animals moving in the pickup range
Wind moving trees/bushes in pick
up range
Picking up cars from the street
Sudden temperature change due
to weather (fans, open windows,
exhaust etc.)
14 Once commissioning of the
BMM 611-... is completed, clip the
module panel onto the module
housing.
Technical data
Photoelectric lighting controller
range: 2 to 300 Lux
Operating voltage: 12 V AC
Operating current: max. 120 mA
Contact type: contact 24 V, 2 A
Switching time: 5 sec to 15 min
Protection system: IP 54
Ambient temperature:
–20 °C to +55 °C
Height of structure (mm): 25
Dimensions (mm) W x H x D:
99 x 99 x 51
Remedy
Mount new fuse
Check terminals
Switch on power
(primary/secondary)
Reset threshold value
Replace bulb
Check/exchange
Replace fuse and check installation
if applicable
Check relay/continuous light switch
Check continuous light switch on
site
Check pick-up area and readjust
switch if necessary, or cover partial
areas
Readjust or cover pickup area
Readjust or cover pickup area
Readjust or cover pickup area
Readjust or cover pickup area
Readjust or cover pickup area