INSTALLATION INSTRUCTIONS
Technical Data / Technische Daten
Isolating spark gap, Class H acc. to EN 62561-3
Type EXFS 100 KU, Part No. 923 101
EXFS 100 KU SN...
II 2 G Ex db IIC T6 Gb
II 2 D Ex tb IIIC T80°C Db
Lightning and surge protection
Certificates:
DEKRA 11ATEX0178 X
IECEx KEM 09.0051X
(s. www.dehn.de)
TC RU C-DE.ГБ06.B.00505
1ExdIICT6
Standards:
for ATEX:
EN 60079-0: 2012
EN 60079-1: 2014
EN 60079-31: 2014
for IECEx:
IEC 60079-0: 2011
IEC 60079-1: 2014
IEC 60079-31: 2013
Ambient temperature range:
-40°C ... +60°C
Parallel installation / Parallel geführter Anbau
Isolating spark gap / Funkenstrecke
Isolierstück
Insulating joint /
Isolierstück
Insulation / Isolierung
B
16 Nm
A
screw M10 / Schraube M 10
A
B
spring washer / Federring
A
Note:
The spark gap can be tested for correct operation by means of a PM 20 test device.
Strictly follow the instructions for use of the PM 20 test device (please refer also to
Publication No. 1608 (latest Update see www.dehn.de)). The spark gap may only be
tested (measured) after in an uninstalled state and outside the Ex zone.
The shrink-on sleeve of the two connecting cables of the spark gap must not be bent.
Hinweise:
Die Funkenstrecke kann mit dem Ableiterprüfgerät PM 20 auf Funktion geprüft
werden. Die Überprüfung darf nur unter Beachtung der Bedienungsanleitung Ableiter-
prüfgerät PM 20 erfolgen (siehe hierzu die entsprechende Publication No. 1608
(aktuelles Update s. www.dehn.de)). Die Überprüfung (Messung) darf nur im ausgebau-
ten Zustand der Funkenstrecke und außerhalb der Ex-Zone erfolgen.
Die beiden Anschlusskabel der Funkenstrecke dürfen im Bereich der Schrumpfmuffe
nicht gebogen werden!
Rated power-frequency withstand voltage/
Bemessungs-Stehwechselspannung
Lightning impulse sparkover voltage/ (1,2/50 µs)
Ansprech-Blitzstoßspannung
Lightning impulse current/ (10/350 µs)
Blitzstoßstrom
Assembly temperature range
Montagetemperaturbereich
Operating temperature range/
Betriebstemperaturbereich
Degree of protection/
Schutzart
Connection/
Anschlussgehäuse
Installation notes / Installationshinweise
Voltage drop at connecting cables depending on the cable length and the impulse current steepness.
Spannungsfall an Anschlußleitungen in Abhängigkeit von der Leitungslänge und der Steilheit des Stoßstroms.
Connecting Cable Length [m] /Länge Anschlussleitung [m]
Voltage Drop [kV] at 10 kA/µs, LPL I /Spannungsfall [kV] bei 10 kA/µs, BSK I
Voltage Drop [kV] at 7.5 kA/µs, LPL II /Spannungsfall [kV] bei 7.5 kA/µs, BSK II 0,8
Voltage Drop [kV] at 5 kA/µs, LPL III / Spannungsfall [kV] bei 5 kA/µs, BSK III
The sum of the voltage drop at the connecting cables and the lightning impulse sparkover voltage must not exceed the insulation strength of the test joint.
Die Summe aus Spannungsfall an den Anschlussleitungen und der Ansprech-Blitzstoßspannung darf die Isolationsfestigkeit der Trennstelle nicht überschreiten.
H
Note: Observe the requirements of AfK recommendation No. 5. (07/2010).
Isolierung
Hinweis: Die Vorgaben entsprechend der AfK-Empfehlung Nr. 5 (07/2010) sind zu beachten.
Requirements on the connecting cables:
• Capable of carrying lightning currents
S
• No ignition sparks
L
• Situated in parallel and as close as possible to the insulating piece
• Connected using the shortest path
• Protected against accidental bridging (for example by means of tools)
Suitable connection points on pipelines are:
• Welded lugs, pins
• Threaded holes in the flanges to receive bolts
• Observe connection clamps / pipe clamps / absence of ignition sparks
U
250 V
w/AC
U
≤ 1,25 kV
r imp
ca. 2000
I
100 kA
imp
-5° ... +50° C
-40° ... +60° C
16
IP 67
M 10
Note:
Deviating dimensional drawing of EXFS 100 KU SN ..., details can be found in the relevant data sheet - SN ...!
Hinweise:
Die Maßzeichnung weicht von EXFS 100 KU SN ... ab, Details sind aus dem jeweiligen Datenblatt SN ... zu entnehmen!
Publication No. 1564 / UPDATE 09.16
Mat. No. 3004676
ca. 4125
0,10 0,20 0,30 0,50 0,75 1,00 1,25 1,50
1,0
2,0
3,1
5,1
7,6
10,1
12,6
15,1
1,5
2,3
3,8
5,7
7,6
9,5
11,4
0,5
1,0
1,5
2,5
3,8
5,1
6,3
7,6
Anforderung Anschlusstechnik
• blitzstromtragfähig,
• zündfunkenfrei,
• unmittelbar parallel und eng am Isolierstück angeordnet,
• auf kürzesten Weg angeschlossen,
• gegen zufälliges Überbrücken (z.B. durch Werkzeuge) gesichert
Geeignete Anschlusspunkte an Rohrleitungen sind
• angeschweißte Fahnen, Bolzen
• Gewindebohrungen in den Flanschen zur Aufnahme von Schrauben
• Anschlußschellen / Bandrohrschelle / Zundfunkenfreiheit beachten
© COPYRIGHT 2016 DEHN + SÖHNE / protected by ISO 16016
ca. 2000
16
2,00 3,00 4,00 4,25
20,2
30,2
40,3 42,8
15,2
22,7
30,3 32,2
10,1
15,1
20,2 21,4
p.t.o.
Safety
Instructions