Tabla Parámetros Para Fuente; Tabla Parámetros Para Fecha - Hora - EUROKLIMAT EKE Serie Manual De Uso Y Mantenimiento

Tabla de contenido

Publicidad

PUESTA EN MARCHA Y PANEL DE MANDO
5.5.6 tabla parámetros para fuente
Param.
PWD
Variable Description
Code
E000
S
E000 - Source pump 1 maintenance hour threshold
E001
S
E001 - Source pump 1 manual mode (modulating)
E002
S
E002 - Source pump 2 maintenance hour threshold
E003
S
E003 - Source pump 2 manual mode (modulating)
E004
S
E004 - Source pump 1 manual mode (on-off)
E005
S
E005 - Source pump 2 manual mode (on-off)
E006
S
E006 - Source fan 1 circuit 1 maintenance hour threshold
E007
S
E007 - Source fan circuit 1 manual mode
E008
S
E008 - Source fan 1 circuit 1 manual mode
E009
S
E009 - Source fan 1 circuit 1 maintenance hour threshold
E010
S
E010 - Source fan circuit 2 manual mode
E011
S
E011 - Source fan 1 circuit 2 manual mode
E012
S
E012 - Source fan temperature threshold for cold climates
E013
S
E013 - Source fan minimum speed for cold climates
E014
S
E014 - Source fan speed up speed for cold climates
E015
S
E015 - Source fan speed up time for cold climates
E016
S
E016 - Enable low noise function
E017
S
E017 - Low noise start hour time band
E017
S
E017 - Low noise start minute time band
E018
S
E018 - Low noise end hour time band
E018
S
E018 - Low noise end minute time band
E019
S
E019 - Low noise fan setpoint in cooling
E020
S
E020 - Source pump flow alarm startup delay
E021
S
E021 - Source pump flow alarm run delay
E022
S
E023 - Source pump delay Off since the compressor Off
E023
S
E022 - Compressor delay On since the source pump On
E024
S
E024 - Source pump rotation time
E025
S
E025 - Source fan setpoint in chiller mode
E026
S
E026 - Source fan setpoint in heatpump mode
E027
S
E027 - Source setpoint offset CH
E028
S
E028 - Source fan setpoint at startup in chiller mode
E029
S
E029 - Source fan startup delay in chiller mode
E030
S
E030 - Source setpoint offset HP
E031
S
E031 - Source fan differential in chiller mode
E032
S
E032 - Source fan differential in heatpump mode
E033
S
E033 - Source inverter fan/pump minimum speed
E034
S
E034 - Source inverter fan/pump maximum speed
E035
S
E035 - Enable source pump run at minimum power/off
E036
S
E036 - Defrost start threshold
E037
S
E037 - Defrost start threshold reset
E038
S
E038 - Defrost start delay
E039
S
E039 - Defrost end threshold
M
E040 - Enable sliding defrost option
E040
E041
S
E041 - Defrost begin delay before actuating the 4 way valve
E042
S
E042 – Defrost ending delay after actuating the 4 way valve
E043
S
E043 - Delay to check for simultaneous defrost
E044
S
E044 - Defrost minimum duration
E045
S
E045 - Defrost maximum duration
E046
S
E046 - Dripping duration
E047
S
E047 - Post dripping duration
E048
S
E048 - Delay between defrosts
E049
S
E049 - BLDC maximum speed in defrost
E050
S
E050 - BLDC minimum speed in defrost
E051
S
E051 - Defrost synchronization type
E052
S
E052 - Delta pressure to reverse the 4 way valve
E053
S
E053 - Antifreeze source alarm threshold
E054
S
E054 - Antifreeze source alarm differential
E055
S
E055 - Antifreeze source alarm delay at 1K below threshold
E056
S
External air temperature - Probe offset
E057
S
Water inlet probe source - Probe offset
E058
M
E058 - Source pump overload input logic (0=NO; 1=NC)
E059
M
E059 - Source pump flow input logic (0=NO; 1=NC)
E060
M
E060 - Source fan output logic (0=NC; 1=NO)
E061
M
E061 - Source pump output logic (0=NO; 1=NC)
M
E062 - Reverse valve output logic (0=NO; 1=NC)
E062
E063
M
E063 - Source analog output type (0=0...10V; 1=PWM)
E064
M
E064 - PWM minimum phase delay
E065
M
E065 - PWM maximum phase delay
E066
M
E066 - PWM pulse width time
E067
M
E067 - Air flow type (0=Independent; 1=Common)
E068
M
E068 - Number of source pumps
E069
M
E069 - Source pump type (0=On/Off; 1=Inverter)
E070
M
E070 - Source fan type (0=Inverter, 1=On/Off)
E071
M
E071 - Unit type (0=Air/Water; 1=Water/Water)
E072
S
E072 – Source fan setpoint type
E073
S
E073 – Minimum envelope setpoint
E074
S
E074 – Maximum envelope setpoint
5.5.7 Tabla parámetros para Fecha - Hora
Param.
PWD
Variable Description
Code
Ga00
S
Ga00 - Date format
Ga01
S
Ga01 - Writing of new day value
50
Type
Default
UoM
UDInt
99000
h
UInt
0
-
UDInt
99000
h
UInt
0
-
UInt
0
-
UInt
0
-
UDInt
99000
h
UInt
0
-
UInt
0
-
UDInt
99000
h
UInt
0
-
UInt
0
-
Real
-5.0
°C/°F
Real
10.0
%
Real
50.0
%
UInt
5
s
Bool
0
-
Int
22
h
Int
0
min
Int
7
h
Int
0
min
Real
45.0
°C/°F
UInt
10
s
UInt
3
s
UInt
10
s
UInt
30
s
UInt
12
h
Real
30.0
°C/°F
Real
10.0
°C/°F
Real
5.0
°C/°F
Real
45.0
°C/°F
UInt
240
s
Real
3.0
°C/°F
Real
15.0
°C/°F
Real
5.0
°C/°F
Real
20.0
%
Real
80.0
%
Bool
0
-
Real
-1.0
°C/°F
Real
1.0
°C/°F
UInt
30
min
Real
52.0
°C/°F
Bool
0
-
UInt
20
s
UInt
30
s
UInt
300
s
UInt
1
min
UInt
5
min
UInt
90
s
UInt
30
s
UInt
20
min
Real
80.0
rps
Real
40.0
rps
USInt
0
-
Real
3.0
bar/psi
Real
-0.8
°C/°F
Real
30.0
°C/°F
UInt
60
s
Real
0.0
°C/°F
Real
0.0
°C/°F
Bool
0
-
Bool
0
-
Bool
0
-
Bool
0
-
Bool
0
-
Bool
0
-
Real
7.0
%
Real
92.0
%
Real
2.5
ms
Bool
0
-
USInt
1
-
Bool
0
-
Bool
0
-
Bool
0
-
USint
0
-
Real
0.0
°C/°F
Real
30.0
°C/°F
Type
Default
UoM
Int
0
-
UInt
0
-
www.euroklimat.it
Range
0....999999
0: Auto; 1:0%;...101:100%
0....999999
0: Auto; 1:0%;...101:100%
0: Auto; 1:Off; 2:On
0: Auto; 1:Off; 2:On
0....999999
0: Auto; 1:0%;...101:100%
0: Auto; 1:Off; 2:On
0....999999
0: Auto; 1:0%;...101:100%
0: Auto; 1:Off; 2:On
-99.9...99.9
0.0...100.0
0.0...100.0
0...300
0:No; 1:Yes
0...23
0...59
0...23
0...59
0.0...999.9
0...999
0...999
0...999
0...999
0...99
-999.9...999.9
-999.9...999.9
0.0...99.9
0.0...999.9
0...999
0.0...99.9
0.0...99.9
0.0...99.9
0.0...100.0
0.0...100.0
0:Wait cond.regul.; 1:Run at min speed
-99.9...99.9
E036...99.9
0...99
-999.9...999.9
0:No; 1:Yes
0...999
0...999
0...99
0...99
0...99
0...999
0...999
0...999
0.0...999.9
0.0...999.9
0:Independent; 1:Separated; 2:Simultaneous
0.0...999.9
-999.9...999.9
0.0...999.9
0...999
-99.9...99.9
-99.9...99.9
0: Alarm if open; 1: Alarm if close
0: Alarm if open; 1: Alarm if close
0:On if close; 1:On if open
0:On if close; 1:On if open
0:Heat if close; 1:Heat if open
0:0...10V; 1:PWM
0.0...100.0
0.0...100.0
0.0...10.0
0=Independent; 1=Common
1...2
0=On/Off; 1=Inverter
0=Inverter, 1=On/Off
0=Air/water; 1=Water/water
0=With envelope; 1=Fixed setpoint
0.0...100.0
0.0...100.0
Range
0:dd/mm/yy; 1:mm/dd/yy;2:yy/mm/dd
1...31
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

Publicidad