8. Main Specifications
Model
Power source
*1
Capacity
*2
Capacity
Allowable external pump head
Temperature range
Sound pressure level (measured 1 m below the unit in an anechoic room)
Water pipe diameter and type
External finish
External dimensions H x W x D
Net weight
Design pressure
Heat exchanger
Compressor
Fan
HIC (Heat inter-changer) circuit
Protection devices
Defrosting method
Refrigerant
SPECIFICATIONS
Power input
Current input
COP (kW/kW)
Power input
Current input
COP (kW/kW)
Inlet water temperature
Outlet water temperature
Outdoor temperature
*1
Inlet
Outlet
R744
Water
Water-side
Air-side
Type
Manufacturer
Starting method
Motor output
Case heater
Lubricant
Air flow rate
Type and quantity
Control and driving mechanism
Motor output
High pressure
Inverter circuit
Compressor
Fan motor
Type and factory charge
Flow and temperature control
3-phase 3-wire 208–230 V 60 Hz
kW
kcal/h
Btu/h
kW
A
kW
kcal/h
Btu/h
kW
A
46–80ºC (when the secondary side control is enabled: 46–70ºC)
115–176ºF (when the secondary side control is enabled: 115–158ºF)
D.B.
dB (A)
mm (in)
mm (in)
mm
in
kg (lbs)
MPa
MPa
Inverter scroll hermetic compressor
MITSUBISHI ELECTRIC CORPORATION
kW
kW
3
m
/min
L/s
cfm
Inverter control, direct driven by motor
kW
High-pressure sensor and switch set at 14 MPa (2030 psi)
Overheat and overcurrent protection
kg
GB-81
QAHV-N136TAU-HPB
40
34400
136480
9.73
30.0 (208 V) 27.2 (230 V)
4.11
40
34400
136480
10.44
32.2 (208 V) 29.1 (230 V)
3.83
68 kPa (22.75 ftAq)
5–63ºC
41–145ºF
-25–43ºC
-13–109ºF
56
*3
19.05 (Rc 3/4"), screw pipe
*3
19.05 (Rc 3/4"), screw pipe
Acrylic painted steel sheet
<Munsell 5Y 8/1 or similar>
1770 x 1220 x 760
69.7 x 48.0 x 29.9
406 (895)
14 (2030 psi)
0.5 (72.5 psi)
Copper tube coil
Plate fins and copper tubes
Inverter
11.0
0.045
PAG
220
3666
7768
Propeller fan x 1
0.75
Copper pipe
Overheat protection
Thermal switch
Auto-defrost mode (Hot gas)
CO
(R744) 6.5 kg (14.3 lbs)
2
LEV