Atlantic VM 050 D400S-3E Manual De Instrucciones página 6

Termo electrico
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 19
installed in volume V2 or the highest possible in
volume V1 for horizontal models.
Position the appliance where it can be accessed.
1.5
Refer to installation figures ❶ & ❷.
1.6
Installation of vertical wall-mounted water heater: To
1.7
facilitate future replacement of the heating element,
leave clear space (300 mm up to 100 litres and 480
mm for higher capacities) below the ends of the
appliance pipes.
The clearance required to install the appliance
1.8
correctly is specified in Figure ❶.
If the appliance is set up in a suspended ceiling or
1.9
attic, or above living space, a drain pan must be
installed underneath the water heater. A drainage
device connected to the sewer system is required.
This product is intended for use at a maximum
1.10
altitude of 2000 m.
This water heater is fitted with a thermostat with an
1.11
operating temperature of more than 60 °C at its
maximum position, capable of reducing the growth of
legionella bacteria in the tank.
CAUTION! Above 50 °C, water could cause
immediate burns. Check the water temperature
before taking a bath or shower.
5

Publicidad

Tabla de contenido
loading

Tabla de contenido