Operating and installation instructions
Redundancy unit for primary switch mode power supplies CP range
Note: These operating and installation instructions cannot claim to contain all detailed information of all types of this product
range and can even not consider every possible application of the products. All statements serve exclusively to describe the
product and have not to be understood as contractually agreed characteristics. Further information and data is obtainable from
the catalogues and data sheets of this product, from the local ABB sales organisations as well as on the ABB homepage www.abb.
com. Subject to change without prior notice.
Additional information relating to cULus approval:
For use in pollution degree 2 environment.
The units need to be mounted in a fire and electrically safe enclosure.
Mounting in horizontal position (input terminals on top).
Information complémentaire relative à la certification cULus:
Pour utilisation dans un environnement de degré de pollution 2.
Les unités doivent être montés dans un coffret offrant une protection électrique et incendie.
La position de montage est horizontale (bornes d'entrée au-dessus).
4.0 x 0.8 mm (0.16 x 0.03") or PH1
10 mm
(0.39")
10 mm
(0.39")
10 mm
(0.39")
Surrounding air temperature:
CP-C.1-A-RU; CP-C.1-A-RU-L: -25 °C to +70 °C operational
CP-C.1-A-RU-C: -40 °C to +70 °C operational
+60 °C to +70 °C derating see table on page 16
For surrounding temperature
use 90 °C - copper wire only
For surrounding temperature > 60 °C up to 70 °C:
use 105 °C - copper wire only
Use only wires with a minimum dielectric strength of 60 V.
1.2 Nm (10.5 lb.in)
2.5...16.0 mm² (12...6 AWG)
2.5...10.0 mm² (12...8 AWG)
2.5...10.0 mm² (12...8 AWG)
60 °C:
2