TANK
6
MANTAINANCE
6.1
ROUTINE MAINTENANCE
Cleaning of the fi lter is carried out with the frequency of at least once a month and anyhow according to the
degree of dustiness of the installation environment.
Remove the metal grille, positioned in the front part (Ref. A) by rotating the screw by one fourth of a revolution in
the anticlockwise direction and pull out the fi lter. Clean the fi lter by washing it with lukewarm water.
CAUTION: Do not use hard brushes or blunt instruments to avoid damaging the fi lter.
Reposition the fi lter and close the metal grille by turning the screw anticlockwise by one fourth of a revolution.
7
DIAGNOSTICS, PROBLEMS, CAUSES AND REMEDIES
7.1
Disadvantages, causes and remedies table
Disadvantages
The display does not
light up
Insuffi cient
water
cooling
Insuffi cient
water
heating
On the display ap-
pears the message
"P1".
On the display ap-
pears the message
"HA".
On the display ap-
pears the message
"LA".
The temperature dis-
played is not the real
one
WARNING: The operator must be able to check, from all the positions to which he has access,
that the plug remains disconnected.
12
C H I L L E R L I N E
Causes
Lack of electric supply
Insuffi cient water fl ow.
Aquarium isolation is
not enough.
Dirty air fi lter
Ambient
temperature
too high
Outgoing air from the
ventilation grid at room
temperature
Obstructed
ventilation
grate
Broken ventilation sys-
tem
Insuffi cient water fl ow
Faulty heater
Damage of the water's
temperature probe.
High water temperature.
Low water temperature.
The water does not cir-
culate correctly inside
the hydraulic circuit
Long and not insulated
pipes
Temperature sensor not
calibrated correctly
Check that the plug is fully inserted in the electrical current
socket.
Check the proper operation of the pump (not supplied)
Insulate the walls of the aquarium and the pipes to reduce
heat loss
Clean the air fi lter following the instruction (Chapter 6 Main-
tenance)
Re-establish the optimal ambient conditions
The maximum ambient temperature allowed is 38°C (100°F)
Lack of gas in the compressor, contact the TECO S.r.l area
retailer
Free the grate or place the unit in a suitable ambient
Contact the TECO S.r.l area retailer
Check the correct operation of the pump (not supplied)
Contact the TECO S.r.l area retailer
Contact the TECO S.r.l area retailer.
Check the correct operation of the pump (not supplied)
Check that there are no crimps in the tubing.
Check that the cooling function is activated.
Check the correct operation of the pump (not supplied)
Check that there are no crimps in the tubing.
Check that the heating function is activated (if present).
Check eventually pipes obstructions
Check the effi ciency of the aquarium's pump (not supplied)
Reduce as much as possible the pipes and insulate them
Calibrate the temperature sensor as described in paragraph
5.2.2 Thermostat Settings
Tab. 7-1
Remedies
EN