24 k vyhlasuje na vlastnú zodpovednosť, že tieto klimatizačné modely, na ktoré sa vzťahuje toto vyhlásenie: 25 w tamamen kendi sorumluluǧunda olmak üzere bu bildirinin ilgili olduǧu klima modellerinin aşaǧıdaki gibi olduǧunu beyan eder: RXTM30N2V1B, RXTM40N2V1B, RXTP25N2V1B, RXTP35N2V1B, ARXTP25N2V1B, ARXTP35N2V1B, 01 are in conformity with the following standard(s) or other 05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s)
Página 3
CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA CE - DECLARATION-DE-CONFORMITE CE - ΔHΛΩΣΗ...
Safety Precautions Read the precautions in this manual This appliance is filled with R32. carefully before operating the unit. • The precautions described herein are classified as WARNING and CAUTION. They both contain important information regarding safety. Be sure to observe all precautions without fail. •...
Página 5
- name, address and day & night telephone numbers for obtaining service. In Europe, EN378 provides the necessary guidance for this logbook. • Sound pressure level is less than 70 dB(A). • Only use accessories, optional equipment and spare parts made or approved by DAIKIN. How to handle the unit WARNING Heat exchanger is sharp, use gloves when handling the unit to avoid injury.
Operation limits Use the system in the following temperature and humidity ranges for safe and effective operation. Cooling Heating Outdoor temperature –10~46°C –25~24°C Indoor temperature 18~32°C 10~30°C Indoor humidity ≤80% To avoid condensation and water dripping out of the unit. If the temperature or the humidity is beyond these conditions, safety devices may be put in action and the air conditioner may not operate.
Outdoor Unit Installation Drawings Max. allowable piping length Wrap the insulation pipe with the finishing tape from bottom Min. allowable piping length 1.5m to top. Max. allowable piping height Additional refrigerant required for refrigerant pipe 20g/m exceeding 10m in length. Gas pipe O.D.
Installation Guidelines • Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airflow, follow the installation guidelines below. • For any of the following installation patterns, the wall height on the outlet side should be 1200mm or less. Wall facing one side Wall facing two sides More than 50...
Outdoor Unit Installation Installing outdoor unit 1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Drawings.” Flaring the pipe end (Cut exactly at 1) Cut the pipe end with a pipe cutter. right angles.) Remove burrs.
Outdoor Unit Installation 3-1 Cautions on pipe handling Wall 1) Protect the open end of the pipe against dust and moisture. Be sure to place a cap. 2) All pipe bends should be as gentle as possible. Use a pipe bender Rain If no flare cap is for bending.
Página 11
Outdoor Unit Installation 1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port. 2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi). (High-pressure valve subsequently requires no operation.) 3) Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg).*1 4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.
Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve cap from liquid stop valve and gas stop valve. Hexagonal 2) Carry out forced cooling operation. wrench 3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
Facility Setting (cooling at low outdoor temperature) This function is designed for facilities such as equipment or computer rooms. It is never to be used in a residence or office where people occupy the space. 1) Cutting jumper 6 (J6) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor temperature drops below –20°C and start back up once the temperature rises again.
Página 14
Wiring WARNING • Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire. • Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
Wiring Wiring diagram Unified Wiring Diagram Legend For applied parts and numbering refer to the wiring diagram sticker supplied on the unit. Part numbering is realized by Arabic numbers in ascending order for each part and is represented in the overview below by symbol “*” in the part code. CIRCUIT BREAKER CIRCUIT BREAKER PROTECTIVE EARTH...
Trial Operation and Testing Trial operation and testing 1-1 Measure the supply voltage and make sure that it falls in the specified range. 1-2 Trial operation should be carried out in either cooling or heating mode. • In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temperature.