10.2 Checklist during commissioning ..........16 Daikin website (publicly accessible). 10.3 To perform a test run..............16 ▪ The full set of latest technical data is available on the Daikin 11 Disposal Business Portal (authentication required). 12 Technical data 12.1 Wiring diagram ................
2 Specific installer safety instructions Unit installation (see "4 Unit installation" [ 4 10]) CAUTION Do NOT open the valves before flaring is complete. This WARNING would cause refrigerant gas leakage. Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable DANGER: RISK OF EXPLOSION legislation.
3 About the box Commissioning (see "10 Commissioning" [ 4 16]) WARNING ▪ If the power supply has a missing or wrong N-phase, DANGER: RISK OF ELECTROCUTION equipment might break down. ▪ Establish proper earthing. Do NOT earth the unit to a DANGER: RISK OF BURNING/SCALDING utility pipe, surge absorber, or telephone earth.
4 Unit installation 4.1.2 Additional installation site requirements >100 >150 of the outdoor unit in cold climates Protect the outdoor unit against direct snowfall and take care that the >50 outdoor unit is NEVER snowed up. >50 >150 >100 >50 >100 (mm) Air outlet...
5 Piping installation Outer diameter Temper grade Thickness (t) (Ø) Ø 6.4 mm (1/4") Annealed (O) ≥0.8 mm 9.5 mm (3/8") Annealed (O) Depending on the applicable legislation and the maximum working pressure of the unit (see "PS High" on the unit name plate), larger piping thickness might be required.
6 Charging refrigerant 5.2.1 To connect the refrigerant piping to the 5.3.2 To perform vacuum drying outdoor unit DANGER: RISK OF EXPLOSION ▪ Piping length. Keep field piping as short as possible. Do NOT start the unit if it is vacuumed. ▪...
7 Electrical installation WARNING Contains fluorinated greenhouse gases RXXX The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the refrigerant leaks in the GWP: XXX room and comes in contact with fire from a burner, a heater, or a cooker, this may result in fire, or the formation of a harmful gas.
8 Finishing the outdoor unit installation WARNING To connect the electrical wiring to ▪ Do NOT use locally purchased electrical parts inside the outdoor unit the product. 1 Remove the service cover. ▪ Do NOT branch the power supply for the drain pump, 2 Open the wire clamp.
There are NO refrigerant leaks. Daikin website (publicly accessible). The refrigerant pipes (gas and liquid) are thermally ▪ The full set of latest technical data is available on the Daikin insulated. Business Portal (authentication required). The correct pipe size is installed and the pipes are properly insulated.
12 Technical data 12.1 Wiring diagram Symbol Meaning Coil Reactor 12.1.1 Unified wiring diagram legend Stepper motor For applied parts and numbering, refer to the wiring diagram on the Compressor motor unit. Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by "*"...