Short>circuit protection:
Degree of protection to
DIN VDE 0660/part 102 A/IEC 60947>4 **
> non>welding
> assignment type 1, 2
Auxiliary circuit
Auxiliary contact block 3TX4
Rated operating voltage
> 230 V
> 400 V
> 500 V
> 690 V
Rated operating voltage
> 24 V
> 48 V
> 110 V
> 220 V
> 440 V
> 600 V
Short>circuit protection:
> Fuse>links
NEOZED and DIAZED, gL (gG)
> Circuit>breaker, C>char.
** Footnote:
According to IEC 60947/VDE 0660, the types of protection mean:
∫Assignment type 1∫: Short circuits can cause damage to the contactors making replacement of the equipment necessary.
∫Assignment type 2∫: Easily separable contact welding but no other damage.
Fuse>links Duty class gL
(gG)
3TF32
3TF33
A
16
16
A
35
50
Rated operating
current I e /AC>15/AC>11
A
5.6
A
3.8
A
2.5
A
1.8
Rated operating
current I e /DC>13/DC>11
A
10
A
4.6
A
0.8
A
0.2
A
0.11
A
0.08
A
16
A
16
Fig. A
L1
CIRCUIT
PROTECTIVE
L2
DEVICE
L3
(IF USED)
FUSE
H4
X1
FUSE
START
STOP
(2)
(1)
44
M
2 WIRE CONTROL (IF USED)
For further data and accessories see Catalog NSK.
M
OLR
T1
M
OLR
T2
PHASE
MOTOR
M
OLR
T3
FUSE
PRI.
H1
X2
SEC.
(3)
OLR
95
96
43
M
A1
A2
3