MYCOMFORT BASE
SELF-DIAGNOSIS PROCEDURE
This procedure allows you to check whether the individual outputs of the
controller function correctly.
To run the procedure, follow the directions below.
> Switch the thermostat off
> Push the
keys at the same time
> Use the
keys to change the value on the display until arriving
at the password for self-diagnosis (
screen will be displayed:
> Press the
button to switch on the various thermostat outputs in
sequence.
Symbol
Actuation
Min. speed
Med. speed
Max. speed
Heating element
Second valve
Extra low speed:
no symbol
The electronic controller outputs can be checked one by one either by
observing the respective component (valve, fan..) or verifying whether a
voltage of 230 V is present at the corresponding terminals.
> To exit the self-diagnosis procedure press
thermostat will automatically exit in any case).
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
level indication:
1= password entry
030
) and press
. The following
Terminals
N-V1
N-V2
N-V3
Valve
N-Vc
N-Vh
no active outlet
(after a few minutes the
ELECTRONIC BOARD (SEE FIGURE 3)
Where:
CI12 DI1-2 Common
DI1
Remote cooling/heating
DI2
Remote On/Off
L
Phase
N
Neutral
PE
Ground
SA
Remote air sensor
SW
Water sensor
V0
-
V1
Low speed. (230 V)
V2
Medium speed (230 V)
V3
High speed (230 V)
Vc
Valve (230 V)
Vh
Heater valve/ Heater/extra-low speed (230 V)
NB
> For power connections use cable w/ cross section size of 1 or 2 mm
> For digital inputs used AWG 24 cable
> For sensor extensions use AWG 24 shielded cable
21
G B
2
FC66002571 - rev. 02